Programming
Master Programming Level
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually resetting
the control panel after each device activation. To enable a device for the Walktest feature, press
1
while viewing
the Edit Detector Screen #3 until the display reads
Walktest Yes
. Each press of the
1
key will cause the display to
toggle between
Walktest Yes
and
Walktest No
. Refer to “Walktest” on page 110.
PAS
The PAS (Positive Alarm Sequence) option will program an automatic, addressable detector to delay panel activation (including alarm relay
and communicator) for a period of 15 seconds plus a programmable time of up to 3 minutes. Zone 047, however, will activate immediately
and may be used to connect a signaling device to indicate PAS activation
(do not use a Notification Appliance Circuit for this purpose)
. To
enable the PAS feature, press
2
while viewing the Edit Detector Screen #3 until the display reads
PAS Yes
. Each press of the
2
key will cause
the display to toggle between
PAS Yes
and
PAS No
. Refer to “Positive Alarm Sequence” on page 109.
For example, if a detector with address 005 is to be configured for PAS operation:
Select
PAS Yes
when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this example Z001
Program an output, such as a control module that is to be activated by detector 005 by assigning the same zone to it; in this example
Z001
Program an output, such as a control module, for PAS activation by assigning zone Z047 to it. This control module may be
connected to a signaling device used to indicate a PAS condition
(do not use a Notification Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone PAS 047 and set the PAS delay timer to some value
With the preceding program settings, when the detector with address 005 is activated, zone Z047 will cause its associated control module to
activate immediately, sounding the connected PAS signaling device. Following the PAS delay time, zone Z001 will cause its associated con-
trol module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both.
Pre-signal
The Pre-signal option programs the detector to delay panel activation for a preprogrammed time delay of up to
three minutes while allowing for visual verification by a person. Note that the alarm relay and communicator
will respond to the initial alarm immediately. In addition, Zone 18 will activate. This zone can be programmed
to a control module which may be used to activate a sounder or indicator which the installer designates as a
Presignal indication
(do not use a Notification Appliance Circuit for this purpose)
. To enable the Pre-signal fea-
ture, press
3
while viewing Edit Detector Screen #3 until the display reads
Pre-signal Yes
. Each press of the
3
key will cause the display to
toggle between
Pre-signal Yes
and
Pre-signal No
. Refer to “Presignal” on page 109.
For example, if a detector with address 005 is to be configured for Pre-Signal operation:
Select
Pre-signal Yes
when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this example Z001
Program an output, such as a control module that is to be activated by detector 005 by assigning the same zone to it; in this example
Z001
Program an output, such as a control module, for Pre-signal activation by assigning zone Z048 to it. This control module may be
connected to a signaling device used to indicate a Pre-signal condition
(do not use a Notification Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone Pre-signal 048 and set the Pre-signal delay timer to some value
With the preceding program settings, when the detector with address 005 is activated, zone Z048 will cause its associated control module to
activate immediately, sounding the connected signaling device to indicate the Pre-signal condition. Following the Pre-signal delay time,
zone Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal, but not both.
Zone Assignment
A maximum of five zones can be programmed to each addressable detector. Pressing
1
while viewing Edit
Detector Screen #4 displays the following screen:
Note that Z*** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z000 for
general alarm zone. A flashing cursor will appear on the first
0
to the right. Enter the three digit number corresponding to the zone that is to
be assigned to this device. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones can
be left blank or programmed as general alarm zone Z000. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Detector Screen #4. Note that the left and right arrow keys can be used to navigate through
the zones and the
CLEAR
key can be used to quickly clear a zone.
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
EDIT DETECTOR
1=ZONE ASSIGNMENT
000
444
444
444
444
Edit Detector Screen #4
Zone Assignment Screen
ZONE ASSIGNMENT
Z000 Z
444
Z
444
Z
444