Honeywell Fire-Lite Alarms CRF-300-6 Installation And Maintenance Instructions Download Page 1

F300-19-00 

I56-1875-006 

BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to 

the  appropriate  Fire•Lite  control  panel  installation  manual  for  detailed  sys

-

tem information. If the modules will be installed in an existing operational 

system, inform the operator and local authority that the system will be tempo

-

rarily out of service. Disconnect the power to the control panel before install

-

ing  the  modules.  This  system  contains  static  sensitive  components.  Always 
ground yourself with a proper wrist strap before handling any circuits so that 
static charges are removed from the body. The module housing should also 

be grounded.

NOTICE: This manual should be left with the owner/user of this equipment.  

GENERAL DESCRIPTION

The CRF-300-6 Six Relay Control Module is intended for use in an intelligent 
alarm  system.  Each  module  is  intended  for  Form-C  switching  applications, 
which do not require wiring supervision for the load circuit. A single isolated 
set  of  dry  relay  contacts  is  provided  for  each  module,  which  is  capable  of 
being wired for either normally open or normally closed for each operation. 
Each module has its own address. A pair of rotary code switches is used to set 

the address of the first module from 01 to 154. The remaining modules are au-

tomatically assigned to the next five higher addresses. Provisions are included 

for disabling a maximum of three unused modules to release the addresses to 
be used elsewhere. Each CRF-300-6 module also has panel controlled green 

LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.

SPECIFICATIONS

Normal Operating Voltage: 

  15-32 VDC

Stand-By Current: 

  1.45 mA

Alarm Current: 

  32 mA (assumes all six relays have been switched once and all six LEDs solid on) 

Temperature Range:   

32°F to 120°F (0°C to 49°C)
Humidity: 

  10 to 93% Non-condensing

Dimensions: 

  6.8˝H × 5.8˝W × 1.0˝D

Accessories: 

  CH-6 Chassis; BB-6 Cabinet; BB-2 Cabinet

Wire Gauge: 

  12-18 AWG

Relay Current: 

  30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control

CRF-300-6 Six Relay Control Module 

Contents include:    

(6) 1 × 3 Terminal Blocks 

(1) 1 × 4 Terminal Blocks

(2) 11/4˝ Stand offs

(4) Machine Screws

(1)  Shunt (NOTE: For the disable position, not more than one shunt shall be 

installed at the same time)

(2) Nuts

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compat

-

ible Fire•Lite system control panel (list available from Fire•Lite).

COMPONENTS

Following are descriptions of the CRF-300-6 mounting frameworks. There are 
two mounting options for CRF-300-6 modules:

 Up  to  six  CRF-300-6  modules  can  be  installed  on  a  CH-6  in  a  BB-6 

• 

cabinet

 One or two CRF-300-6 modules can be installed in a BB-2 cabinet

• 

WARNING

All relay switch contacts are shipped in the standby state (open) state, but 
may have transferred to the activated (closed) state during shipping. To en

-

sure that the switch contacts are in their correct state, modules must be made 
to communicate with the panel before connecting circuits controlled by the 

module.

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

3 A

30 VDC

Resistive

Non-coded

2 A

30 VDC

Resistive

Coded

.9 A

110 VDC

Resistive

Non-coded

.9 A

125 VDC

Resistive

Non-coded

.5 A

30 VDC

Inductive (L/R=5ms)

Coded

1 A

30 VDC

Inductive (L/R=2ms)

Coded

.3 A

125 VAC

Inductive (PF=.35)

Non-coded

1.5 A

25 VAC

Inductive (PF = .35)

Non-coded

.7 A

70.7 VAC

Inductive (PF=.35)

Non-coded

2 A

25 VAC

Inductive (PF=.35)

Non-coded

I56-1875-006

INSTALLATION ANd MAINTENANCE INSTRUCTIONS

One FireLite Place

Northford, CT 06472

Phone: 203.484.7161 

firealarmresources.com

Summary of Contents for Fire-Lite Alarms CRF-300-6

Page 1: ...arm Current 32 mA assumes all six relays have been switched once and all six LEDs solid on Temperature Range 32 F to 120 F 0 C to 49 C Humidity 10 to 93 Non condensing Dimensions 6 8 H 5 8 W 1 0 D Accessories CH 6 Chassis BB 6 Cabinet BB 2 Cabinet Wire Gauge 12 18 AWG Relay Current 30 mA Relay Pulse 15 6 mS pulse duration pulse under panel control CRF 300 6 Six Relay Control Module Contents includ...

Page 2: ...les wide and two modules deep Figure 1 CH 6 Chassis The BB 2 cabinet has a built in chassis that will accommodate one or two CRF 300 6 modules Figure 2 BB 2 Cabinet 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 BASE ADDRESS ADDRESS DISABLE NONE ONE TWO THREE 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 BASE ADDRESS ADDRESS DISABLE NONE ONE TWO THREE The front CRF 300 6 mod...

Page 3: ...d addressing do not set the lowest address above 94 4 A shunt is provided to disable a maximum of three unused modules Modules are disabled from the highest address and work downward If two modules are disabled the lowest four addresses will be functional while the highest two will be disabled For example if the shunt for Ad dress Disable is placed on two and the base address switch is set to 28 t...

Page 4: ...f the NEC For easier wiring assign all power limited wiring to one side rather than alternating with non power limited PROGRAMMING The CRF 300 6 module operates with the following Fire Alarm Control Panels MS 9200 MS 9600 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 N C N O COMMON ADDRESS 5 N C N O COMMON ADDRESS 4 N C N O COMMON ADDRESS 3 N C N O COMMON ADDRESS 2 N C N O COMMON ADDRE...

Reviews: