OPERATION

Large particles (lint and hair) are caught in the pre-filter. As 
the dirty air passes through the intense high-voltage 
electric field surrounding the ionizer wires, all particles are 
given an electrical charge. The air then moves through the 
collector part of the cell where alternate parallel plates are 
charged positively and negatively, creating a uniform 
electrostatic field. The charged particles are attracted to 
and collect on the plates that have the opposite electrical 
charge. The air leaving the air cleaner has fewer particles. 
Each time the air circulates through the F58, more 
particles are removed.

CHECKOUT

Inspecting Installation

Make sure:
• Sheet metal joints between air cleaner and duct are 

sealed.

• All sheet metal connections are complete.
• Outside air, if used, is mixed with return air or heated, as 

necessary, before it can reach the air cleaner.

• Airflow arrows on the electronic cell point downstream.
• Electronic cell and pre-filter are clean and dry.

Checking Air Cleaner Operation

With all components but UVC tube in place, turn on the air 
cleaner switch and energize the power supply. Check the 
following points of operation:

1.

ON indicator is lit. CHECK indicator comes on if there 
is a problem with the high voltage power supply.

2.

With the air cleaner energized, push the Test button. 
A snapping sound indicates that the collector voltage 
is present on the cell. CHECK indicator comes on 
when the Test button is held down.

3.

If operation is not as described, refer to the Trouble-
shooting section.

4.

Insert UVC to into the lamp-holder per tube replace-
ment (page 11).

WARNING

Before cleaning or other maintenance, the 
appliance must be disconnected from the supply 
mains.

SERVICE

CAUTION

Sharp Edges.
Can cause personal injury.

Wear protective gloves to prevent cuts from sharp 
metal edges.

Cleaning Cells and Pre-filters

To assure optimum performance from the air cleaner, the 
cells and pre-filters must be cleaned regularly, every one to 
six months. WASH indicator on some models lights to 
indicate it is time to wash the pre-filters and cells.

IMPORTANT

 Do not wash the pre-filter in an automatic dish-
washer. Vacuum or brush the pre-filter or soak it in 
a tub.
Do not use coil cleaner on air cleaner cells.

Cleaning Cells in Automatic 
Dishwasher

CAUTION

Burn Hazard.
Can cause personal injury.

Hot water can accumulate in tubes supporting 
collector plates; tip cells to drain water from tubes.
Allow cells to cool completely in dishwasher at end 
of wash cycle or wear protective gloves to avoid 
burns.

IMPORTANT

— Check your dishwasher Owner’s Guide. Some man-

ufacturers do not recommend washing electronic 
cells in their dishwasher.

— If your dishwasher has upper and lower arms, posi-

tion the cells carefully to allow good water circula-
tion. 

— Be careful to avoid damaging the cells when placing 

them in the dishwasher. Broken ionizer wires or bent 
collector plates are not included in the Warranty.

— Very dirty cells can discolor the plastic parts and lin-

ing of some dishwashers. This discoloration is not 
harmful. To minimize it, wash the cells more fre-
quently or try a different brand of dishwasher deter-
gent.

— Do not allow the dishwasher to run through the dry 

cycle. This bakes on any contaminants not removed 
during the wash cycle and reduces air cleaner effi-
ciency.

To clean cells in dishwasher:

1.

Put the cells on the lower rack of the dishwasher with 
the airflow arrow pointing up. It may be necessary to 
remove the upper rack. Do not block water flow to the 
upper arm.
HINT: Lay a few large water glasses between the 
spikes on the lower rack and rest the cells on them so 
the spikes do not damage the aluminum collector 
blades.

Summary of Contents for F58G

Page 1: ...ir cleaners Solid state power supply is self regulating and maintains peak efficiency during a wide range of cell dirt loading conditions Indicator lights signal proper operation and fault conditions May be connected to a building management system Relay closure occurs when fault occurs or when cells need cleaning Galvanized cabinet protects against rust Test button checks system operation Pre fil...

Page 2: ...tronic Cell each 9 3 16 lb 4 2 kg Shipping Weight F58G 42 lb 19 1 kg F58H 26 7 lb 12 1 kg F58G UV 46 lb 20 9 kg Installed Weight Cells Included F58G 37 lb 16 8 kg F58H 24 lb 10 9 kg F58G UV 41 lb 18 6 kg Dimensions See Fig 3 and Fig 4 Accessories 202614 Carbon Filter 13643AA Ionizer Wires quantity 5 32350736 001 UV tube Repair Parts See Parts List section Regulatory Approvals Ozone free UV tube me...

Page 3: ...at various airflow rates FRACTIONAL EFFICIENCY PARTICAL DIAMETER Pm EFFICIENCY RATINGS BASED ON AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR CONDITIONING ENGINEERS STANDARDS 52 2 2012 10 1 0 1 100 80 60 40 20 0 0 0 AIR FLOW RATE IN CFM cum hr PRESSURE DROP IN in wc Pa 0 1 24 9 0 2 49 8 0 3 74 7 0 4 99 5 0 5 124 4 2000 3400 500 850 1000 1700 1500 2500 2500 4250 ...

Page 4: ...NTED ELECTRONIC AIR CLEANER 31 00442 01 4 Fig 3 F58G Installation dimensions of electronic air cleaner in in mm Shown with UV lamp optional Fig 4 F58H Installation dimensions of electronic air cleaner in in mm 6 3 4 171 13 25 32 350 24 610 3 8 10 ...

Page 5: ...team coils with a freeze up control Choosing Mounting Position WARNING Heavy Equipment Hazard Can cause injury or equipment damage Mount the air cleaner with the power supply on top Do not mount the air cleaner with the pre filter facing down the latches may not hold and the cell and pre filter can fall unexpectedly WARNING Be careful of damage to equipment Ultraviolet light can cause color fading...

Page 6: ...ring normal operation of HVAC equipment Fig 6 Changing duct size gradually to minimize turbulence INSTALLATION When Installing This Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a...

Page 7: ...ion When properly installed the actuator on the pre filter is inserted into the wiring tray of the air cleaner Rotate the latch to secure the pre filter in place WIRING WARNING Electric Shock Hazard Can cause personal injury Be sure line voltage power source is the same as the voltage and frequency listed on the air cleaner label Power supply wiring system shall provide a disconnect switch for all...

Page 8: ...W VOLTAGE CONNECTION TO BUILDING MANAGEMENT SYSTEM OR PLUG INTO ADJACENT UNIT 24V A C OR 24V D C 2A MAXIMUM STATUS INDICATION LED TWO OR THREE 5 4 3 2 1 INSTALL JUNCTION BOX ON THE END OF EACH ROW 6 JUNCTION BOX 6 ON OFF SWITCH INTERLOCK SWITCH SWITCH OFF WHEN REMOVING PRE FILTER AND SWITCH ON WHEN PRE FILTER INSTALLED CONNECT TO MAIN POWER OR PLUG INTO ADJACENT UNIT LOW VOLTAGE CONNECTION TO BUIL...

Page 9: ...supply mains SERVICE CAUTION Sharp Edges Can cause personal injury Wear protective gloves to prevent cuts from sharp metal edges Cleaning Cells and Pre filters To assure optimum performance from the air cleaner the cells and pre filters must be cleaned regularly every one to six months WASH indicator on some models lights to indicate it is time to wash the pre filters and cells IMPORTANT Do not wa...

Page 10: ...cells and pre filters in a final clear water rinse for ten minutes 7 Wipe the ionizer wires and contact board on the end of the cell using your thumb and forefinger with a small damp cloth 8 Make sure to dry the cells before inserting back into the air cleaner Reinstalling Cells and Pre filters Insert the electronic cell with the contact board up and the air flow arrow pointing downstream Tilt the...

Page 11: ...Electric Shock Hazard Can cause personal injury Disconnect power before opening power supply cover The electronic air cleaner generates a small amount of ozone in normal operation During the first week or two of operation the amount may be higher because of sharp edges on some of the new high voltage metal parts Normal use quickly dulls these edges The average person can detect the odor of ozone i...

Page 12: ...Checkout section i This function does not apply to F58G1016E F58G1016EUV F58G1024E and F58G1024EUV Fig 14 Moving EFFY shorting bar to reduce ozone production about 20 to 25 percent ELECTRICAL TROUBLESHOOTING WARNING Electric Shock Hazard Can cause personal injury or equipment damage The following procedures expose hazardous live parts and are for use only by qualified personnel Disconnect power be...

Page 13: ...ECTION CELL FRAME AND COLLECTOR SECTION CELL SHORTED INFINITE RESISTANCE REPLACE CELL CELL OK REPLACE POWER SUPPLY M13460 FOLLOW THE STEPS IN ORDER DO NOT SKIP AROUND EACH TIME YOU ISOLATE AND FIX A PROBLEM GO BACK TO START REPEAT ALL THE STEPS UNTIL THE AIR CLEANER CHECKS OUT OK 1 2 3 THIS STEP EXPOSES DANGEROUSLY HIGH VOLTAGE ONLY A QUALIFIED SERVICE TECHNICIAN SHOULD ATTEMPT THIS STEP WARNING C...

Page 14: ... V a c 50 Hz CE version 42009287APE 5 Interlock Switch 196277 6 Power Switch 203321 7 Contact Board Assembly 32003893 001 8 Building Management Interface Circuit Board with ON CHECK and with WASH functions with BMS F58G1016 50043779 001U Building Management Interface Circuit Board with ON CHECK functions without WASH without BMS F58G1024 32003942 001U 9 UV Tube 32350736 001 U 10 Ballast 32350743 0...

Page 15: ... F58H Replacement Parts Reference No Description Part Number 1 Prefilter 50081476 002 2 Electronic Cell FC37B1030 U 3 Contact Board Assembly 32003893 001 4 Interlock Switch 196227 Optional Accessories not shown in diagram Ionizer Wires Quantity 5 136434AA Carbon Filter Only applicable for NON UV version 202614 3 4 2 1 ...

Page 16: ...mber 9439 92 1 may be contained in these products above the threshold level of 0 1 by weight of the listed article Honeywell Part Number 32000392 585 32000392 601 32000388 401 32000388 709 32000392 451 32000392 689 32000388 422 32000392 251 32000392 385 32002633 004 32000388 481 32000392 373 32000388 447 32000384 211 32000388 709 32000392 389 32000392 466 32000384 301 32000392 251 32000392 401 320...