5.5.5 PGM block icons
The following table summarizes the various appearances that a PGM block can assume based on configuration,
view, and current operating state.
If icon is...
Then it represents...
And Module State is...
Project view
gray
PGM is configured for non-redundant
operation
N/A
gray/white
PGM primary configured for redundant
operation
N/A
white/gray
PGM secondary configured for redundant
operation
N/A
Monitoring view
green
PGM is non-redundant
Run
green/white
Primary PGM is synchronized
Run
white/green
Secondary PGM is synchronized
Backup
green/yellow
Primary PGM is not synchronized and
partner PGM is visible
Run
yellow
PGM is non-redundant
No Database
yellow/shadow
Primary PGM is synchronized
No Database
yellow/yellow
Primary PGM is not synchronized and
partner PGM is visible
No Database
red
PGM is non-redundant and not
communicating
Offnet
red/white
Primary PGM is not communicating
Offnet
white/red
Secondary PGM is not communicating
Offnet
5.5.6 PGM block diagnostic alarms
When active, the PGM block reports the following diagnostic alarms.
Attention
In a redundant PGM, if a PB Link failure occurs in the secondary PGM, the secondary PGM does not generate an
alarm or an event. However, there is a diagnostic that detects the absence of the primary master on the field network
and prohibits the synchronization. You can also refer to the redundancy history for more details.
Alarm
Description
Communication Error
This alarm is reported when the connection between the PGM and
slave devices is broken.
The following are the probable causes for generation of this alarm.
•
Power is disrupted to the IOTA in which the PGM resides.
•
The PGM is removed under power.
•
The FTE cables are removed from the IOTA.
5 PROFIBUS GATEWAY MODULE (PGM) BLOCK
40
www.honeywell.com
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...