9.4 Configuring a PIOMB
Prerequisites
• The field network configuration in the PBLink block must be complete.
• The DSBs must be configured.
• The PIOMB must be assigned to the C300CEE.
Perform the following steps to configure a PIOMB
1
Drag-and-drop the PIOMB from the PGM_IF library to the CEE of the C300 Controller.
You can also click
File
>
New
>
I/O Modules
>
PGM_IF
>
PIOMB
and create a new PIOMB.
Attention
When you create a PIOMB, it resides in the Unassigned folder in the Project tree. You must drag-and-drop it to the
CEE of the C300 Controller.
2
The
Name New Function Blocks
dialog box appears.
3
In the
Destination
column, you can accept the default name or change the name if required and click
Finish
.
The PIOMB block appears under the I/O of C300CEE.
4
Double-click the PIOMB.
The PIOMB block configuration form appears.
5
In the
Tag Name
field, type the name of the PIOMB (a maximum of 16 characters) or accept the default.
6
In the
Item Name
field, type the item name.
7
In the
Description
field, type a brief description of up to 132 characters.
8
Click the point picker button next to the
PDC Name Reference
box.
The
Point Selection
dialog box appears.
You can view the following information from the
Point Selection
dialog box.
•
Points
- Displays the tag name of the DSB block assigned to a PBLink of a PGM.
•
Types
- Displays the DSB template name. For example, GENDSBDP.
•
Controller Name
- Displays the PGM tag name to which the DSB is assigned.
•
Link/EE Name
- Displays the PBLink tag name to which the DSB is assigned.
Attention
The
Point Selection
dialog box also displays the PDC description that you have provided while configuring the
PDC tab.
9
Select the PDC to be associated to the PIOMB.
Attention
•
You can associate a PDC to a unique PIOMB. To associate another PDC, you must drag-and-drop a new
PIOMB from the PGM_IF library or create a new PIOMB.
•
You can assign/unassign a PDC to a PIOMB even if the DSB is in the QVCS checked-in status.
•
After you associate a PDC to a PIOMB, you cannot view the specific PDC in the
Point Selection
dialog box.
•
In a CEAGDSB, the PDC associated with the CEAG Communication module cannot be associated with a
PIOMB.
•
You cannot associate a
Gateway Status
or a
Gateway Command
PDC to a PIOMB since these PDCs do not
send any process data to controller. If you try to associate a
Gateway Status
or a
Gateway Command
PDC to
a PIOMB, an error message appears.
10
Click
OK
.
9 PROFIBUS I/O MODULE (PIOMB) FUNCTION BLOCK
221
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...