9.1
Periodic Checks
The following table identifies checks that you should make periodically (every 3 to 6
months) to keep the C300 Controller in good working condition.
Check . . .
Possible Corrective Action . . .
That all segments of the 4-character
display and the light emitting diodes
(LED) on C300 Controller are working.
If segment or LED is not lit or has
dimmed, you must replace the C300
Controller, since front-panel indicators
and LEDs are not field replaceable.
That all connections are secure.
Secure connections, as needed.
That cable insulation is not worn or
cracked.
Replace cables, as required.
That IOTA is secure.
Tighten mounting screws.
9.2
Recommended Spare Parts
The following table provides a list of parts that you may want to keep on hand for
backup.
ATTENTION
Since aging occurs, even if the batteries have been regularly recharged
throughout their lifetime, the 24 Volt Battery, Honeywell part number
51199946-100 should be replaced after every two years of operation.
Part Name
Part Number
Description
Quantity
per 10/100
C300 Controller
8C- or 8U-PCNT02
C300 Controller Module
1/5
C300 IOTA
8C- or 8U-TCNT01
C300 Controller Input Output
Terminal Assembly
1/2
Fuse
51506348-341
800 mA, quick-acting fuse on Input
4/25