33-00135EFS—05
14
TROUBLESHOOTING
NOTE: Disconnect RedLink™ when making changes to the
device.
RESET PROCEDURE:
Hold down the “Connect” button on the ERM for 10 seconds. The
“Connection” LED should appear red for a few seconds and go out. This
indicates the unit is reset.
Symptom
Possible Cause
Action
Relays don’t switch as
expected
Incorrect jumper
configuration
Check jumper
configuration. If
incorrect, unenroll
from system, change
jumper, then re-enroll
with system.
Connected LED is red Loss of
communication with
system
Verify thermostat and/
or Equipment Interface
Module are powered
and functioning
correctly.
Connected LED is off
Device is not enrolled
with system
Enroll with system.
No LEDs are on
No power to device
Verify 24 VAC at R/C
terminals.