EK280
Application Manual
27
4.4 HF pulse input with automatic conversion
Pulses from a high-frequency pulse generator can be counted by the EK280 only when an external power
supply exists, i.e., not during battery operation. To ensure uninterrupted gas volume measurement, the
EK280 can be configured so that it switches to a low frequency pulse generator in the event of failure of the
external power supply.
When the power supply is functioning, volumes and loads (Vb, Vm, Qb, Qm) will be measured with the high
frequency pulse generator (priority input). In the event of failure of the high frequency pulse generator (e.g.,
due to failure of the external power supply), the EK280 automatically continues to measure with the low
frequency transmitted (fail safe input).
4.4.1 Pulse generator connection
Danger!
For EK280 with internal power supply, the mains voltage must be switched off before
opening the housing, ensure it is not turned back on and verify that there is no voltage.
DE1
DE2
+ - + -
+ -
LF Pulse
generator
(reed contact)
Pulse generator
HF
(Namur)
−
Connect the gas meter's low frequency pulse generator (LF reed contact) to terminal "DE1" of the
EK280.
−
Connect the gas meter's high frequency pulse generator (HF Namur) to terminal "DE2" of the
EK280. Respect polarity, i.e. connect the impulse generator's "+" to the "DE2 +" terminal and "-" with
"DE2 -".
−
Release the inputs 1 and 2 (terminal "DE1" and "DE2") calibration seals.