L7148F ELECTRONIC AQUASTAT

®

 CONTROLLER

3

68-0189—2

Immersion Well: 

Available separately. Contact your 

distributor or Honeywell sales representative to order, or 
refer to Accessories for Immersion Wells, Compression 

Fittings, and Element Holders, form 68-0040.

Transformer: 

Available separately with either quick connect 

terminals or AMP plug connections. Contact your 
distributor or Honeywell sales representative to order.

Table 1. Sensor Specifications.

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury or 
death.

Use this product only in systems with a pressure 

relief valve.

WARNING

Electrical Shock Hazard.

Can cause electrical shock or equipment damage.

Disconnect power supply before beginning wiring.  

Never apply a jumper across (or short) terminals 

B1 and B2. This will burn out the transformer.

Mounting

WARNING

Fire or Explosion Hazard.

Can cause serious injury, death or property 
damage.

Sensor must be fully inserted to bottom of well.

IMPORTANT

The L7148F is not designed for spud mounting to the 

sensing well.

Sensor and immersion well are not provided and must be 

purchased separately. Mounting screws must be obtained 
locally. See Table 1 for sensor specifications. The sensor 

is adaptable to existing immersion wells with a shell I.D. of 

3/8 in. (10 mm). To order an immersion well, contact your 
distributor or Honeywell sales representative, or refer to 

Accessories for Immersion Wells, Compression Fittings, 

and Element Holders, form 68-0040.

In new and replacement applications, mount the Electronic 
Aquastat Controller on the vestibule away from heated 

surfaces. Use four no. 6 screws, obtained locally, to mount 

the control through the four mounting holes.

Mount the immersion well, purchased separately, where boiler 

water of average temperature can circulate freely around it.

To insert the immersion well into the boiler:

1.

Turn off all power and drain the boiler.

2.

If no tapping is provided, prepare properly sized and 

threaded tapping near the top of the boiler.

3.

Coat the well threads sparingly with pipe dope, install 
the well in the boiler tapping, and tighten securely.

4.

Refill the boiler and check for water leakage.

Sensor

Termination

Lead Length

Diameter Capsule Length

Mounting

Material

32004955-001 One 1/4 in. (6 mm) and one 3/16 in. 

(5 mm) quick connect terminal.

12 in. (304 mm), 

18 gauge wire.

3/8 in. 

(10 mm)

1-1/4 in. 

(32 mm)

Compression Thermal 

plastic

32004955-002

18 in. (458 mm), 

18 gauge wire

32004955-003

25 in. (610 mm), 

18 gauge wire.

32004955-004

36 in. (914 mm), 

18 gauge wire

32004955-005

48 in. (1219 

mm), 18 gauge 

wire.

Summary of Contents for Electronic Aquastat L7148F

Page 1: ...ck connect or AMP plug connections T TV and Z terminals are provided in a terminal block with screw connections Vent damper plug optional Separate high limit control not required Software defined minimum maximum limit settings External 120 Vac to 24 Vac transformer ordered separately is field replaceable and upgradable Patented limit rated 209659A B C Sensors are separately replaceable Communicati...

Page 2: ...d feature modules L7148F Electronic Aquastat Controller with AMP plug connections with or without vent damper plug and communications port for adding advanced feature modules AMP connector on wiring board for transformer connection High Limit Setpoint Range 130 F to 240 F 54 C to 116 C Select models may be different Differential Fixed 10 F 6 C Select models may be different Operating Voltage Range...

Page 3: ...om of well IMPORTANT The L7148F is not designed for spud mounting to the sensing well Sensor and immersion well are not provided and must be purchased separately Mounting screws must be obtained locally See Table 1 for sensor specifications The sensor is adaptable to existing immersion wells with a shell I D of 3 8 in 10 mm To order an immersion well contact your distributor or Honeywell sales rep...

Page 4: ...tions 1 Strip 1 16 in of insulation from the wire end 2 Insert the wire under the terminal screw and contact plate 3 Using a standard flat headed screwdriver tighten the screw until the wire is firmly in contact with the screw and contact plate 4 Tighten the screw an additional one half turn For quick connect terminal connections Connect the quick connect to the appropriate terminal on the control...

Page 5: ...l exits the high limit state and returns to the normal state when the temperature of the boiler drops to the high limit setting minus 10 F 12 C 3 Reset Detects an error condition such as an open sensor and shuts down all outputs The control continues to function and automatically restarts if the error condition is corrected High Limit The high limit switch shuts off the burner B1 B2 output when th...

Page 6: ...ON B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS 1 2 3 4 5 6 7 M11475B L1 HOT L2 1 4 3 TR TH TH TR T87F ZONE 3 T87F ZONE 2 T87F ZONE 1 END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F COM L7148F HIGH LIMIT...

Page 7: ... 2 L1 L2 DISCONNECT SWITCH 1 6 TO ADVANCED FEATURE MODULE TO BOILER SENSOR 24V COM L2X L1X C R 5 OPTIONAL VENT DAMPER PLUG C1 G L1 C2 L2X L1X B2 B1 R C R DATA PORT STATUS THERMOSTAT C W R S1 S2 4 4 4 4 4 3 3 TR TH THTR LOW VOLTAGE GAS VALVE VR8300 L1 HOT L2 1 1 2 2 3 3 4 4 4 4 3 4 5 6 5 1 2 4 6 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND...

Page 8: ...ENSOR 120V L2X L1X C R 3 OPTIONAL VENT DAMPER PLUG COM BURNER CONTROL 24V HOT TO VALVE OR IGNITION CONTROL C1 G L1 C2 L2 L2X L1X B2 B1 R C R DATA PORT STATUS THERMOSTAT C W R S1 S2 5 5 5 5 5 4 4 L1 HOT L2 1 1 2 3 1 2 3 1 2 3 1 2 3 CIRCULATOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERM...

Page 9: ...NT DAMPER IS PLUGGED INTO L7148F FUSE BLOWS WHEN THERMOSTAT FIRST CLOSES AFTER FUSE BLOWS L7148F OPERATES ONLY WHEN VENT DAMPER IS CONNECTED SEE VENT DAMPER PRODUCT SPECIFICATIONS FOR INTERNAL SCHEMATICS S1 IS A 3 16 INCH QUICK CONNECT TERMINAL S2 IS 1 4 INCH THIS DEVICE HAS AMP PLUGS C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION...

Page 10: ...NS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION R882C IS PROVIDED WITH NEC CLASS 1 ENCLOSURE B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTR...

Page 11: ...REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C Z B2 G ARE ALL CONNECTED INSIDE DEVICE FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS 1 2 3 4 5 6 M11479B 24 VOLT COMMON 24 VOLT HOT EFT OUTPUT 24 VOLT THERMOSTA...

Page 12: ... STARTS THERMOSTAT OR THERMOSTAT WIRING PROBLEM CHECK SYSTEM PER INSTRUCTIONS PROVIDED WITH THERMOSTAT NO NO YES NO YES CHECK L7148F DIAGNOSTIC LED FLASHING TWO BLINKS CHECK SENSOR CONNECTIONS IF GOOD REPLACE SENSOR THREE OR FOUR BLINKS INTERNAL ERROR REPLACE L7148F L7148F IN RESET MODE WAIT FIVE MINUTES FOR CONTROL TO RESET VENT DAMPER OPEN CHECK FOR 24V AT B1 B2 YES CHECK VENT DAMPER CABLE AND C...

Reviews: