Installation
“U” Style DIN Rail
“G” Style DIN Rail
Panel
Panel
Panel
Terminal Connectors
View from End
Front View
View from End
Front View
Barriers, Repeater, Isolators
Hose Clamp Slot
for Pipe Mounting
Metal clip for
“U” DIN rail mounting
Gray clip for
“G” DIN rail mounting
Mounting Kit
(Hose Clamp
included in kit)
Through Hole for
DIN Rail Mounting
Figure 2-4 Remote Mounting Hardware
2.3 Conduit connections
The DirectLine provides a male ½” NPT thread to accommodate a customer conduit
connection. Use ½” conduit coupling (min. 38.1mm (1.5”) long) on DL conduit
connection to clear cordset connector. Conduit can not be used with field wiring
connector (see Figure 2-2) due to size restriction.
Do not exceed 200in-lb. torque when attaching fixed piping.
Use wrench flats provided under the ½” NPT threads to support the DirectLine
during installation.
9/11
DirectLine® DL423 Sensor Module User Manual