USA-3

USA

CAN

MEX

D

Wiring

 CAUTION

To ensure that the DG..T is not damaged during op-

eration, note the switching capacity, see page 
(Technical data).

 

In the case of low switching capacities, such as 
24 V, 8 mA, for example, we recommend using 
an RC module (22 Ω, 1 μF) in air containing 
silicone or oil.

 1 

  Disconnect the system from the electrical power 

supply.

½" NPT Conduit:

ø 

0.4" (10 mm)

2

NO

1

NC

3

COM

½" NPT

2

NO

3

COM

1

NC

3

4

2

5

 

DG..FT, DG..NT: the NO-to-COM connection 
is interrupted if the pressure drops (contacts 

3

 

and 

2

 open).

 

 DG..T, DG..HT: the NC-to-COM connection is 

interrupted if the pressure rises (contacts 

3

 and 

1

 open).

Adjustment

 

The switching point is adjustable via hand wheel.

 1 

  Disconnect the system from the electrical power 

supply.

 2 

 Detach the housing cover.

 

Tightening torques, see Technical Information 

bulletin DG at www.docuthek.com.

 3 

 Connect an ohmmeter.

NO

2

NC

1

COM

3

COM

3

NC

1

NO

2

0

0.4" = 0.4"WC

(1 cm = 1 mbar)

 4 

 Set the switching point using the hand wheel.

 5 

 Connect a pressure gauge.

NO

2

NC

1

COM

3

COM

3

NC

1

NO

2

0

0.4" = 0.4"WC

(1 cm = 1 mbar)

 6 

 Apply pressure. In doing so, monitor the ohm-

meter and the pressure gauge.

Pressure switches without manual reset 

(DG..T, DG..FT, DG..ST)

Type

Adjusting  

range* 

"WC 

(mbar)

Mean  

switching 

differential  

at min. 

and max. 

setting  

"WC 

(mbar)

Max. inlet 

pressure p

max.

 

psi (mbar)

No 

venting 

line

With 

venting 

line

1)

DG 6T

0.2 – 2.4 

(0.5 – 6)

0.08 – 0.12 

(0.2 – 0.3)

2.4 psi 

(165)

8.5 psi 

(600)

DG 10T

0.4 – 4 

(1 – 10)

0.1 – 0.16 

(0.25 – 0.4)

7 psi 

(480)

DG 50T

1 – 20 

(2.5 – 50)

0.4 – 0.8 

(1 – 2)

DG 150T 12 – 60 

(30 – 150)

1.2 – 2 

(3 – 5)

DG 500T 40 – 200 

(100 – 500)

3.2 – 6.8 

(8 – 17)

Pressure switches with manual reset 

(DG..HT, DG..NT)

Type

Adjusting  

range* 

"WC 

(mbar)

Reset 

pressure**  

"WC 

(mbar)

Max. inlet 

pressure p

max.

 

psi (mbar)

No 

venting 

line

With 

venting 

line

1)

DG 10T

0.4 – 4 

(1 – 10)

0.16 – 0.4 

(0.4 – 1)

7 psi

(480)

8.5 psi 

(600)

DG 50T

1 – 20 

(2.5 – 50)

0.4 – 0.8 

(1 – 2)

DG 150T 12 – 60 

(30 – 150)

0.8 – 4.8 

(2 – 12)

DG 500T 40 – 200 

(100 – 500)

2 – 7.2 

(5 – 18)

1)

 

 

Connect the venting line to port 4. Connections, 

see page 2 (Installation).

*   Adjusting tolerance = ± 15% of the scale value.
**  Difference between switching pressure and pos-

sible reset.

 

If the DG..T does not trip at the desired switch-
ing point, correct the adjusting range using the 
hand wheel. Relieve the pressure and repeat 
the process.

Summary of Contents for DG T Series

Page 1: ...th socket IP 65 1 2 1x NPT connection 2x NPT connections K2 T2 N Red green pilot LED for 24 V DC AC Red green pilot LED for 110 to 230 V AC Blue pilot lamp for 120 V AC A External adjustment If none this specification is omitted DG T switches with rising pressure Part designations 1 2 3 5 4 1 Upper housing section with cover 2 Lower housing section 3 Hand wheel 4 NPT conduit coupling 5 Manual rese...

Page 2: ...rtical diaphragm Then the switching point pS corresponds to the scale value SK set on the hand wheel In other installation positions the switching point pS will change and no longer correspond to the scale value SK set on the hand wheel Check the switching point ps SK ps SK 0 08 WC ps SK 0 08 WC CAUTION If port 4 is at the top IP 65 will not be satisfied 4 IP65 The DG T must not be in contact with...

Page 3: ...0 0 4 0 4 WC 1 cm 1 mbar 6 Apply pressure In doing so monitor the ohm meter and the pressure gauge Pressure switches without manual reset DG T DG FT DG ST Type Adjusting range WC mbar Mean switching differential at min and max setting WC mbar Max inlet pressure pmax psi mbar No venting line With venting line1 DG 6T 0 2 2 4 0 5 6 0 08 0 12 0 2 0 3 2 4 psi 165 8 5 psi 600 DG 10T 0 4 4 1 10 0 1 0 16 ...

Page 4: ...tching point minus the pressure differential between the switching pressure and possible lock off For details of the pressure differential between the switching pressure and possible reset see table on page 3 Adjustment Tightness test 1 Shut off the downstream gas pipeline close to the valve 2 Open the valve and the gas supply Check all used ports for tightness N2 13 psi max 29 psi 15 min 3 4 Main...

Page 5: ... medium and ambient temperatures 40 to 140 F 40 to 60 C Long term use in the upper ambient temperature range accelerates the ageing of the elastomer ma terials and reduces the service life please contact manufacturer The set switching point may palpably change in me dia and ambient temperatures below 22 F 30 C Storage temperature 4 to 104 F 20 to 40 C Diaphragm pressure switch silicone free Diaphr...

Page 6: ...omplete see page 1 Part designa tions Report any transport damage immediately Storage Store the product in a dry and clean place Storage temperature see page 5 Technical data Packaging The packaging material is to be disposed of in accordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Directive on the restriction o...