DACT-E3 Product Installation Document —
P/N 9000-0581:J6 12/16/2019
9
Table 4.2.1.1 lists the DACT-E3 Contact ID Event Reporting Codes for the Standard Formats.
Event
SIA
Contact ID
4/2
3/1
(Standard DACT Reporting Formats)
Fire Alarm (Smoke or Manual Station)
FA [GGT]
1 110 [0G] [GGT]
0 [T]
0
Fire Alarm Restored
FH [GGT]
3 110 [0G] [GGT]
2 [T]
2
Waterflow Alarm Silenceable
FA [GGT]
1 110 [0G] [GGT]
0 [T]
0
Waterflow Alarm Non-Silenceable
SA [GGT]
1 113 [0G] [GGT]
0 [T]
0
Waterflow Alarm Restored Silenceable
FH [GGT]
3 110 [0G] [GGT]
2 [T]
2
Waterflow Alarm Restored Non-Silenceable
SH [GGT]
3 113 [0G] [GGT]
2 [T]
2
CO/Gas Alarm
GA [GGT]
1 151 [0G] [GGT]
2 [T]
0
CO/Gas Alarm
GH [GGT]
3 151 [0G] [GGT]
2 [T]
2
Trouble (except Waterflow or Special AMM/PID)
FT [GGT]
1 373 [0G] [GG0]
8 [T]
8
Trouble Restored
FJ [GGT]
3 373 [0G] [GG0]
7 [T]
7
Trouble (Waterflow AMM/PID)
ST [GGT]
1 370 [0G] [GG0]
8 [T]
8
Trouble Restored (Waterflow AMM/PID)
SJ [GGT]
3 203 [0G] [GG0]
7 [T]
7
Trouble (Special AMM/PID)
UT [GGT]
1 370 [0G] [GG0]
8 [T]
8
Trouble Restored (Special AMM/PID)
UJ [GGT]
3 370 [0G] [GG0]
7 [T]
7
Supervisory / Tamper (Module)
SS [GGT] 1 203 [0G] [GGT]
6 [T]
6
Supervisory Restored (Module)
SR [GGT]
3 203 [0G] [GGT]
7 [T]
7
PAS/Action/Supervisory (Sensor)
FS [GGT]
1 200 [0G] [GGT] 6 [T]
6
PAS/Action/Supervisory Restored (Sensor)
FR [GGT]
3 110 [0G] [GGT]
7 [T]
7
Disable (except Waterflow or Special AMM/PID) FB [GGT]
1 571 [0G] [GGT]
8 [T]
8
Disable Restored
FU [GGT]
3 571 [0G] [GGT]
7 [T]
7
Disable (Waterflow AMM/PID)
SB [GGT]
1 570 [0G] [GGT]
8 [T]
8
Disable Restored (Waterflow AMM/PID)
SU [GGT] 3 570 [0G] [GGT]
7 [T]
7
Disable (Special AMM/PID)
UB [GGT]
1 570 [0G] [GGT]
8 [T]
8
Disable Restored (Special AMM/PID)
UU [GGT]
3 570 [0G] [GGT]
7 [T]
7
AC Fail
AT 0
1 301 [0G] [000]
80
8
AC Fail Restored
AR 0
3 301 [0G] [000]
70
7
Phone Line 1 Fault
LT 1
1 351 [0G] [000]
81
8
Phone Line 1 Fault Restored
LR 1
3 351 [0G] [000]
71
7
Phone Line 2 Fault
LT 2
1 352 [0G] [000]
82
8
Phone Line 2 Fault Restored
LR 2
3 352 [0G] [000]
72
7
Automatic Test (NORMAL)
RP 0
1 602 [0G] [000]
90
9
Automatic Test (With Exception)
RP 991
1 602 [0G] [991]
91
9
Begin Programming
LB [GG3]
1 627 [0G] [GG3]
93
9
End Programming
LX [GG3]
3 628 [0G] [GG3]
73
7
E3 Series Releasing (Standard DACT Reporting Formats)
Trouble (Releasing Device) (Supervisory)
FS [GG3]
1 200 [0G] [GG3]
6 [3] 6
Trouble (Releasing Device) (Supervisory Restoral) FR [GG3]
3 200 [0G] [GG3]
7 [3]
7
Pre-Alarm (Action Supervisory)
FS [GG3]
1 200 [0G] [GGZ]
6 [3]
6
Pre-Alarm (Action Restoral)
FR [GG3]
3 200 [0G] [GGZ]
7 [3]
7
Pre-Release (Alarm)
FA [GG1]
1 110 [0G] [GG1]
0 [1]
0
Pre-Release (Alarm Restoral)
FR [GG1]
3 110 [0G] [GG1]
2 [1]
2
Release (Alarm)
FA [GG1]
1 110 [0G] [GG1]
0 [1]
0
Release (Alarm Restoral)
FR [GG1]
3 110 [0G] [GG1]
2 [1]
2
Abort (Supervisory)
FS [GG3]
1 200 [0G] [GG3]
6 [3]
6
Abort (Supervisory Restoral)
FR [GG3]
3 200 [0G] [GG3]
7 [3]
7
Manual Dump (Alarm)
FA [GG1]
1 110 [0G] [GG1]
0 [1]
0
Manual Dump (Alarm Restoral)
FR [GG1]
3 110 [0G] [GG1]
2 [1]
2
Table 4.2.1.1 DACT-E3 Contact ID Event Reporting Codes for Standard Formats