Table 4.2.2.1 lists the DACT-E3 Contact ID Event Reporting Codes for the Custom Formats.
Event
SIA
(See Note 2)
Contact ID
4/2
(See Note 3)
3/1
(Custom DACT Reporting Formats)
Fire Alarm (Smoke or Manual Station)
FA (UUU)
1 110 (NN) (UUU)
0 (U)
0
Fire Alarm Restored
FH (UUU)
3 110 (NN) (UUU) 2 (U)
2
Waterflow Alarm Silenceable
FA (UUU)
1 110 (NN) (UUU)
0 (U)
0
Waterflow Alarm Non-Silenceable
SA (UUU)
1 113 (NN) (UUU)
0 (U)
0
Waterflow Alarm Restored Silenceable
FH (UUU)
3 110 (NN) (UUU)
2 (U)
2
Waterflow Alarm Restored Non-Silenceable
SH (UUU)
3 113 (NN) (UUU)
2 (U)
2
CO/Gas Alarm
GA (UUU)
1 151 (NN) (UUU)
0 (U)
0
CO/Gas Alarm
GH (UUU)
3 151 (NN) (UUU)
2 (U)
2
Trouble (except Waterflow or Special AMM/PID) FT (UUU)
1 373 (NN) (UUU)
8 (U)
8
Trouble Restored
FJ (UUU)
3 373 (NN) (UUU)
7 (U)
7
Trouble (Waterflow AMM/PID)
ST (UUU)
1 370 (NN) (UUU)
8 (U)
8
Trouble Restored (Waterflow AMM/PID)
SJ (UUU)
3 203 (NN) (UUU)
7 (U)
7
Trouble (Special AMM/PID)
UT (UUU)
1 370 (NN) (UUU)
8 (U)
8
Trouble Restored (Special AMM/PID)
UJ (UUU)
3 370 (NN) (UUU)
7 (U)
7
Supervisory / Tamper (Module)
SS (UUU)
1 203 (NN) (UUU)
6 (U) 6
Supervisory Restored (Module)
SR (UUU)
3 203 (NN) (UUU)
7 (U)
7
PAS/Action/Supervisory (Sensor)
FS (UUU) 1 200 (NN) (UUU)
6 (U)
6
PAS/Action/Supervisory Restored (Sensor)
FR (UUU)
3 110 (NN) (UUU)
7 (U)
7
Disable (except Waterflow or Special AMM/PID) FB (UUU)
1 571 (NN) (UUU)
8 (U)
8
Disable Restored
FU (UUU)
3 571 (NN) (UUU)
7 (U)
7
Disable (Waterflow AMM)
SB (UUU)
1 570 (NN) (UUU)
8 (U)
8
Disable Restored (Waterflow AMM/PID)
SU (UUU)
3 570 (NN) (UUU)
7 (U)
7
Disable (Special AMM/PID)
UB (UUU)
1 570 (NN) (UUU)
8 (U)
8
Disable Restored (Special AMM/PID)
UU (UUU)
3 570 (NN) (UUU)
7 (U)
7
AC Fail
AT 0
1 301 (NN) (UUU)
80
8
AC Fail Restored
AR 0
3 301 (NN) (UUU)
70
7
Phone Line 1 Fault
LT 1
1 351 (NN) (UUU)
81
8
Phone Line 1 Fault Restored
LR 1
3 351 (NN) (UUU)
71
7
Phone Line 2 Fault
LT 2
1 352 (NN) (UUU)
82
8
Phone Line 2 Fault Restored
LR 2
3 352 (NN) (UUU)
72
7
Automatic Test (NORMAL)
RP 0
1 602 (NN) (UUU)
90
9
Automatic Test (With Exception)
RP 991
1 602 (NN) (UUU)
91
9
Begin Programming
LB (900)
1 627 (NN) [900]
90
9
End Programming
LX (900)
3 628 (NN) [900]
70
7
E3 Series Releasing (Custom DACT Reporting Formats)
Trouble (Releasing Device) (Supervisory)
FS [UUU]
1 200 [NN] [UUU]
6 [U]
6
Trouble (Releasing Device) (Supervisory Restoral)
FR [UUU]
3 200 [NN] [UUU]
7 [U]
7
Pre-Alarm (Action Supervisory)
FS [ZZZ]
1 200 [NN] [ZZZ]
6 [Z]
6
Pre-Alarm (Action Restoral)
FR [ZZZ]
3 200 [NN] [ZZZ]
7 [Z]
7
Pre-Release (Alarm)
FA [ZZZ]
1 110 [NN] [ZZZ]
0 [Z]
0
Pre-Release (Alarm Restoral)
FR [ZZZ]
3 110 [NN] [ZZZ]
2 [Z]
2
Release (Alarm)
FA [ZZZ]
1 110 [NN] [ZZZ]
0 [Z]
0
Release (Alarm Restoral)
FR [ZZZ]
3 110 [NN] [ZZZ]
2 [2]
2
Abort (Supervisory)
FS [ZZZ]
1 200 [NN] [ZZZ]
6 [Z]
6
Abort (Supervisory Restoral)
FR [ZZZ]
3 200 [NN] [ZZZ]
7 [Z]
7
Manual Dump (Alarm)
FA [ZZZ]
1 110 [NN] [ZZZ]
0 [Z]
0
Manual Dump (Alarm Restoral)
FR [ZZZ]
3 110 [NN] [ZZZ]
2 [Z]
2
Table 4.2.2.1 DACT-E3 Contact ID Event Reporting Codes for Custom Formats