STRYKER CVAHU ZIO CONFIGURATION GUIDE
26
Figure 30: Parameter Temp Sp Stby Clg
STBY CLG:
Displays and allows modification of
standby cooling setpoint. Its value ranges from OCC
CLG to UNOC CLG.
Figure 31: Parameter Temp Sp Stby Htg
STBY HTG:
Displays and allows modification of
standby heating setpoint. Its value ranges from OCC
HTG to UNOC HTG.
Figure 32: Parameter Temp Sp Setpoint
SETPOINT:
Displays and allows modification of
centre setpoint read from wall module. Its value
ranges from CNTSP LO to CNTSP HI.
Figure 33: Parameter Temp Sp Frz Prtc
FRG PRTC:
Displays and allows modification of
Space freeze protection setpoint. Its value ranges
from 30 to 70. The space heating setpoint is shifted to
this value when a window is opened.