Honeywell CTS-V Series Installation Instructions Download Page 1

INSTALLATION INSTRUCTIONS

31-00144-02

20

Solid and Split Core 0-5/10Vdc 
Output Current Sensors

CTS-V AND CTP-V SERIES

APPLICATION

The 0-5/10Vdc Output Solid and Split Core Current 
Sensors are designed for use in any AC current 
monitoring application in which you are looking to 
monitor a particular piece of equipment.

 SPECIFICATIONS

Monitored Current Type: 

AC Current

Maximum AC Voltage: 

600 VAC

Isolation Voltage: 

2200 VAC

Supply Voltage:

Induced from the Monitored Conductor (Insulated 

Conductors only)

150-Amp Sensors: 0 to 10 VDC

Operating Temperature Range: 

5 to 104ºF (-15 to 

40ºC)

Operating Humidity Range: 

0 to 95%, non-con-

densing

Storage Temperature: 

41 to 95°F (5 to 35°C)

RH Range: 

40% to 85% RH, non-condensing

Wire Recommendations: 

2 Conductor (Shielded 

Cable)

Wire Size:

18 to 24 AWG (0.823 mm

2

 to 0.205 mm) Copper 

Wires only

Terminal Block Torque Rating: 

4.43 to 5.31 in-lbs. 

(0.5 to 0.6 Nm)

Minimum Mounting Distance:

1” (2.6 cm) between current sensor & other magnetic 

devices (Relays, Contactors, Transformers)

Agency Approvals:

UL/CUL US Listed (UL 508) Ind. Control Equipment 

(File # E309723), CE, RoHS2, WEEE

STANDARD ORDERING

Table 1. Standard Ordering.

WARNING

This product is not intended to be used for 
Life or Safety applications.

This product is not intended for use in any 
hazardous or classified locations. The CTS-V 
and CTP-V Series Current Sensors must be 
used on Insulated Conductors Only!

WARNING

Electrical shock hazard.

Disconnect and lock out all power sources 
before installation as severe injury or death 
may result from electrical shock due to 
contact with high voltage wires.

Model #

Selectable Ranges Measurement

AC Waveform

Solid-Core Split-Core

Output 

Signal

CTS-V-50

0 to 10/20/50A

Average

Pure Sinusoidal

0 to 5 VDC

CTS-V-150 0 to 50/100/150

Average

Pure Sinusoidal

0 to 10 VDC

CTP-V-50

0 to 10/20/50A

Average

Pure Sinusoidal

0 to 10 VDC

CTP-V-150 0 to 50/100/150

Average

Pure Sinusoidal

0 to 10 VDC

Summary of Contents for CTS-V Series

Page 1: ...g 4 43 to 5 31 in lbs 0 5 to 0 6 Nm Minimum Mounting Distance 1 2 6 cm between current sensor other magnetic devices Relays Contactors Transformers Agency Approvals UL CUL US Listed UL 508 Ind Control Equipment File E309723 CE RoHS2 WEEE STANDARD ORDERING Table 1 Standard Ordering WARNING This product is not intended to be used for Life or Safety applications This product is not intended for use i...

Page 2: ...he cover to close the current sensor An audible click will be heard as the tab slides over the tongue on the base CAUTION Mating surfaces of the magnetic core are exposed when the sensor is open Electrical contact grease present on the cores to prevent corrosion can capture grit and dirt if care is not exercised Operation can be impaired if anything prevents good contact between pole pieces Visual...

Page 3: ...ing center Do not dispose of with household waste Do not burn M37360 SHIELDED CABLE SIGNAL COMMON 0 5 0 10 VDC ANALOG INPUT GND SHIELD PLC DDC OR DATA ACQUISITION SYSTEMS Problem Solution No reading Verify that there is current flowing through the conductor being monitored with a clamp on current probe The power for the current sensor is induced from the conductor being monitored Check the polarit...

Page 4: ...REGULATORY INFORMATION FCC REGULATIONS 15 19 A 3 This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation IC REGULATIONS RSS GEN This device complies with Industry Canada s license exempt RS...

Reviews: