Honeywell CRIR E1 User Manual Download Page 1

USER GUIDE FOR THE

COMMERCIAL CARBON DIOXIDE SENSOR,

400 PPM TO 2000 PPM (UP TO 5000 PPM

EXTENDED RANGE),

 CRIR E1

000841

Issue 1

TABLE OF CONTENTS

1.0  GENERAL INFORMATION .............................................. 1
2.0  SENSOR HANDLING ........................................................ 3
3.0  AUTOMATIC BASELINE CORRECTION ....................... 3
4.0  TERMINATION ................................................................... 3
5.0  CALIBRATION..................................................................... 6
6.0  SELF-DIAGNOSTICS............................................. ............6 
7.0  MODBUS REGISTER DEFINITION............................... ..6
8.0  MODBUS FUNCTION DESCRIPTION........................ ....9

1.0 

GENERAL INFORMATION

The CRIR E1 Commercial Carbon Dioxide (CO

2

) sensor is a 

single channel, non-dispersive infrared (NDIR) sensor. Within 
the CRIR E1 is a sensing chamber with an infrared source at 

TABLE 1. SPECIFICATIONS
CHARACTERISTIC

PARAMETER

Target gas

carbon dioxide (CO

2

)

Operating principle

non-dispersive infrared (NDIR)

Standard range

1, 2

400 ppm to 2000 ppm, up to 5000 ppm extended range

Measurement interval

4 s

Accuracy

3

±5

0 ppm 

±5

% of reading

Typical response time (T

90

<120 s

Sensor warm-up time

3 minimum typical

Repeatability

>97% 

Operating voltage

4.5 V to 5.5 V unprotected against surges and reverse connection

Power consumption

300 mA peak, 30 mA average

Alarm output, open collector

1000 ppm/800 ppm normal state is conducting maximum 100 mA.
Transistor open at CO

2

 high or at sensor failure (see Figure 1).

Serial communication

5

UART, Modbus protocol

Operating temperature range

0°C to 50°C

Storage temperature range

-40°C to 70°C

Operating humidity

0 %RH to 90 %RH non-condensed

Expected operating life

10 years

Maintenance

6

maintenance-free for normal indoor applications 

Weight

<8 g

Dimensions

33 mm x 22 mm X 11,2 mm (tolerance ±0,5 mm)

1

 The CRIR E1 is designed to measure CO

2

 in the range of 400 ppm to 2000 ppm with the accuracy specified in Table 1; however, exposure to 

concentrations below 400 ppm may result in incorrect operation of the ABC algorithm and should be avoided when the ABC is ON.

2

 The CRIR E1 provides readings via UART in the extended range; however, the accuracy is reduced.

3

 In normal IAQ applications, the sensor accuracy is defined after a minimum of three ABC periods of continuous operation.

4

 The sensor accuracy is specified over the operating temperature range and referenced to certified calibration mixtures. Uncertainty of calibration 

gas mixtures (±1% currently) is to be added to the specified accuracy for absolute measurements.

5

 See Sections 7.0 and 8.0 for Modbus address and parameter definitions.

6

 The CRIR E1 normally does not require maintenance in IAQ applications; however, for some industrial applications, maintenance may be required.

one end and a detector fitted with an optical filter at the other 
end. The source emits radiation at wavelengths which include 
the absorption band of CO

2

. The filter blocks wavelengths which 

are not sensitive to the presence of CO

2

, thereby increasing 

selectivity and sensitivity. As the light passes through the 
sensing chamber, a fraction is absorbed if CO

2

 is present. The 

difference between the light emitted by the source and received 
by the detector can then be converted to a CO

2

 concentration 

reading. The Automatic Baseline Correction (ABC) function can 
automatically calibrate the sensor’s lowest reading over a pre-
configured interval to 400 ppm CO

2

. This enhances long term 

stability and may eliminate the need for calibration. 

See Tables 1 and 2, and Figures 1 and 2 for specifications and 
mounting and dimensional diagrams. 

Summary of Contents for CRIR E1

Page 1: ...re CO2 in the range of 400 ppm to 2000 ppm with the accuracy specified in Table 1 however exposure to concentrations below 400 ppm may result in incorrect operation of the ABC algorithm and should be avoided when the ABC is ON 2 The CRIR E1 provides readings via UART in the extended range however the accuracy is reduced 3 In normal IAQ applications the sensor accuracy is defined after a minimum of...

Page 2: ...00 R0 50 Center of gas inlet holes 10 16 2 54 2 54 7 62 29 70 4 50 2 50 4 50 2 50 0 64 8 02 0 64 16 50 1 2 3 4 5 8 7 6 9 5 19 dia TABLE 2 PINOUT PIN NUMBER FUNCTION 1 DAC 2 UART_RXD 3 UART_TXD 4 UART_R T 5 bCAL_in CAL_in 6 PWM output 7 Alarm output 8 GND 9 Vin_ 4 5 V to 5 5 V FIGURE 1 ALARM STATE DIAGRAM CO2 concentration ppm Alarm state open FIGURE 2 MOUNTING DIMENSIONS FOR REFERENCE ONLY MM ...

Page 3: ... the expected CO2 concentration in fresh air thus compensating for sensor drift Table 3 shows the ABC period specifications Please refer to Section 8 0 Modbus Function Description for setting the ABC period TABLE 3 ABC PERIOD SPECIFICATION CHARACTERISTIC PARAMETER ABC periods1 4 hr to 4800 hr default is 180 hr 1 ABC periods can be configured per the user s requirements The available range is four ...

Page 4: ...down absolute maximum voltage range1 GND to VDD 0 5 V internal pull up to VDD resistor 120 k output low level1 0 4 VDC maximum at 8 mA sink output high level1 2 4 VDC minimum at 8 mA source 4 UART_R T direction control line for half duplex RS485 transceiver like MAX 485 configured as digital output no internal protection pulled down at processor reset power up and power down absolute maximum volta...

Page 5: ...er s microcontroller or to provide analog output no internal protection pulled down at processor reset power up and power down normal concentration range 400 ppm to 2000 ppm PWM cycle time 1004 ms 5 beginning of each cycle high level output 2 ms end of each cycle low level output 2 ms relationship between CO2 concentration ppm and PWM output C CO2 2000 x TH 2 TH TL 4 TH time ms of high level outpu...

Page 6: ... CO2 sensor exposure 5 2 Modbus Calibration Two Modbus calibration types are offered Background calibration Requires the sensor to be exposed to fresh air 400 ppm CO2 Second point calibration Requires the sensor to be exposed to a certain atmosphere with a steady CO2 concentration other than 400 ppm and that this CO2 concentration should be informed via Modbus communication to the sensor For more ...

Page 7: ...High5 Sensor ID high5 IR15 14 Sensor ID Low5 Sensor ID low5 IR16 15 Serial Num 1 Serial Num 1 corresponding to the ASCII red 2 digit code Default ASCII 000 0000 000 IR17 16 Serial Num 2 Serial Num 2 corresponding to the ASCII red 2 digit code default ASCII 000 0000 000 IR18 17 Serial Num 3 Serial Num 3 corresponding to the ASCII red 2 digit code Default ASCII 000 0000 000 IR19 18 Serial Num 4 Seri...

Page 8: ...gal data address exception HR14 13 Reserved returns illegal data address exception HR15 14 Reserved returns illegal data address exception HR16 15 Reserved returns illegal data address exception HR17 16 Reserved returns illegal data address exception HR18 17 Reserved returns illegal data address exception HR19 18 Reserved returns illegal data address exception HR20 19 Reserved returns illegal data...

Page 9: ...01100000 the 0th bit of the data bit is DI1 the first bit of the data bit is DI2 and so on The valid bits are as follows DI 6 Out of Range DI 7 Memory error 8 1 3 Read Output Status Master Transmit FE 04 00 06 00 01 C5 C4 Slave Reply FE 04 02 00 03 ED 25 Data Explain 00 03 is valid data 0x0003 the binary is 0b11 The valid bits are as follows DI 1 Alarm Output status inverted due to Open Collector ...

Page 10: ...33 it means sensor ID 8 1 10 Read Serial Number Master Transmit FE 04 00 0F 00 05 14 05 Slave Reply FE 04 0A 53 43 30 37 31 31 30 33 30 33 C4 D6 Data Explain 53 43 30 37 31 31 30 33 30 33 is valid data 0x53433037313130333033 After conversion to ASCII it is SC07110303 8 2 Holding Registers Description Values are read and written from IR using Read holding registers function code 03 8 2 1 Setup ABC ...

Page 11: ...valid data 0x0190 decimal is 400 ppm 8 2 5 Setup User Acknowledgement Master Transmit FE 06 00 05 00 00 8D C4 Slave Reply FE 06 00 05 00 00 8D C4 Data Explain 00 00 is valid data 0x0000 it means to clear the calibration completion flag 8 2 6 Setup User Special Command Master Transmit FE 06 00 06 7C 01 9C C4 Slave Reply FE 06 00 06 7C 01 9C C4 Data Explain 7C 01 is valid data 0x7C01 it means to sta...

Page 12: ...y to determine the suitability of the product in the application Specifications may change without notice The information we supply is believed to be accurate and reliable as of this writing However Honeywell assumes no responsibility for its use Honeywell serves its customers through a worldwide network of sales offices and distributors For application assistance current specifications pricing or...

Reviews: