Honeywell ControLinks R7999A Manual Download Page 11

R7999A,B CONTROLINKS™ CONTROLLER

11

65-0238—10

CHECKOUT AND 

TROUBLESHOOTING

Fault Codes

The R7999 ControLinks™ Controller is designed so that only 

an unrecoverable internal related fault will cause lockout. 

The R7999 will recycle when specific external problems are 

detected and then cleared.

When the R7999 locks out, obtain the fault code (a repeating 

series of blinks from the POWER LED) by pressing and holding 

the Reset button. To interpret the LED flashes, for example, a 

Fault 11 would be one slow blink and one fast blink, while a 

Fault 67 would be six slow blinks followed by seven fast blinks.

See Table 7 for fault codes and descriptions. The fault code 

with text description can be observed using the laptop 

computer commissioning tool, or a touchscreen display.

Table 7. Fault Listings and Descriptions.

Fault/

Blink 

Code

Description

Corrective Action

11

Device is operating properly.

13

MV input energized at an improper time.

Reset control. Check Burner Control Interface wiring and correct error. 

This error causes the device to remain in initiate state at power up.

14

HF and LF are energized at the same time.

Reset control. Check Burner Control Interface wiring and correct error. 

This error causes the device to remain in initiate state at power up.

15

Transition to the requested Burner Control input state is not allowed 

from the current state. E.g. Standby to Modulate, RUN/TEST between 

modes, of limits are interrupted is not allowed.

R7999 is checking the following inputs: LF, HF, MV, LCI and outputs: 

LFP, HFP, and LCO. If any of these inputs/outputs are in the wrong state, 

this fault will occur.

Reset control. Check wiring to burner control and R7999.

Moving a RM7800 Run/Test switch to Test will induce this fault during 

commissioning mode.

21

Internal error—Time Base (Microprocessor test failed).

Reset control

a

22

Internal error—Safety relay (internal safety relay test failed).

Reset control

a

23

Internal error—Safety relay (internal safety relay test failed).

Reset control

a

24

Internal error—Time storage (Microprocessor test failure).

Reset control.

a

25

Internal error—Limited move (Actuator moving to a position

during commissioning mode).

Reset control.

a,c

 Check the feedback pot on the actuator indicated by 

the LED

26

Internal error—Targeted move (actuator moving to a position,but not 

getting to the postions).

Reset control.

a,c 

(Can get this if you push the CW/CCW buttons on the 

actuator after commissioning is done)

27

Internal error—LVD (low voltage detect, the R7999 has detected a low 

voltage condition of less than 98 vac).

Reset control.

a

28

Internal error—ISR check (internal safety relay check, microprocessor 

check).

Reset control.

a

31

Internal fault—A2D Range (analog to digital actuator feedback pot 

shorted or out of range).

Reset control.

Check actuator wiring; see Channel LED for actuator at fault.

32

Internal fault—A2D cross-matching error (happens after 

commissioning process has been completed, and the burner control 

has been given a call for heat - terminal 14 high).

Reset control.

a

33

Internal fault—LCO Drive (terminal 14 is off when it should be on. 

Check terminal 14 for 120vac. Internal relay could be welded or 

shorted).

Reset control.

a

 Replace the R7999.

34

Internal fault—LCO/I Feedback (terminal 14 is on when it should be off. 

and LCI terminal 13 is off).

1. Reset control

b

.

2. Terminal 14 has voltage present from external source; correct 

wiring error.

3. Make sure that short does not exist at terminal 14. Control will need 

replacement if a sustain fault code 34 exists after steps 1, 2 and 3 are 

performed.

35

Internal fault (safety relay feedback - check for noise induced from the 

system).

Reset control.

a

36

Fuel selection error.

1.Check wiring through fuel select switch. Only one fuel can be 

selected at any one time. This error causes the device to remain in 

initiate state.

2. No fuel selected. Correct by selecting fuel.

37

Fault—HFP or LFP output.

Verify correct wiring from the R7999 terminals 8 and 9 to burner 

control; specifically check wiring at LFP and HFP.

38

Internal Fault—Memory curve.

Reset control.

a

 (Micro bad, replace R7999)

39

Internal Fault—AC sampling.

Reset control.

a

Summary of Contents for ControLinks R7999A

Page 1: ...mable behaviors of all actuators during Purge and Standby Programmable behavior of nonselected fuel actuator Independent lightoff and minimum modulation positions Wide power voltage input range 50 60 Hz two models cover global applications Auto Manual input Manual mode firing rate input Pluggable controller to wiring subbase Multipurpose communications port Field configurable device Integrated boi...

Page 2: ...t Control OUT LCO R7999A 120 Vac 8 0A run 42A inrush UL R7999A 120 Vac 6 0A run 26A inrush CE R7999B 240 Vac 4 0A run 26A inrush CE Alarm ALR R7999A 120 Vac 1A pilot duty UL R7999A 120 Vac 1 0A at PF 0 4 6A inrush CE R7999B 240 Vac 1 0A At PF 0 4 6A inrush CE High Fire HFP R7999A 120 Vac 1A pilot duty UL R7999A 120 Vac 1A at PF 0 4 6A inrush CE R7999B 240 Vac 1A at PF 0 4 6A inrush CE Light Off Po...

Page 3: ...9 Wiring Subbase There is no direct wiring to the controller Tables 1 and 2 provide the R7999 input and output terminal descriptions respectively Table 3 provides the R7999 maximum field wiring lengths A block hookup diagram for the ML7999 Actuator is shown in Fig 2 and typical wiring diagrams are shown in Fig 4 5 or 6 Earth Ground Earth ground is required for proper operation of the ControLinks s...

Page 4: ...13 Line voltage input that signals limits are satisfied and that a demand exists to run the burner Provides power to energize Burner Control Voltage present equates to function selected Feedback Air Damper CW S CCW 17 18 19 Provides position feedback for the Air actuator CW Clockwise rotational endpoint of the feedback potentiometer S Variable resistance signal from potentiometer CCW Counterclockw...

Page 5: ... position 5 Processing Demand State The R7999 enters this state when the LCI has just become active The R7999 makes sure the firing rate command inputs are valid before advancing to the next state 6 Run State The R7999 enters this state when the LCI input is active The high fire or low fire command from the burner control causes the air actuator and the FGR actuator if configured to drive to the p...

Page 6: ...r wire Make sure that all mechanically tightened joints along the ground path are free of nonconductive coat ings and protected against corrosion on mating surfaces b Follow local and NEC 1 codes cImplies no limitations beyond voltage current times resistance drop considerations versus wire size constraints dRequires ground shield at controller end See Fig 2 4 e Ground shield to digital ground ter...

Page 7: ...commended as interface wiring If using a USB port a Keyspan or Belkin USB to RS 485 converter is recommended The R7999 requires the presence of one of the Fuel Select inputs to start communications with the ZM7999 ControLinks Commissioning Software Additional wiring interface requirements include that HF and LF command inputs cannot be activated at the same time NOTE A stack gas analyzer is requir...

Page 8: ...mV 1 1 1 1 1 1 2 3 4 4 3 2 2 GROUND SHIELD TO SUBBASE EARTH GROUND SCREW ON LOW VOLTAGE SIDE OF SUBBASE FUSE LINE VOLTAGE TO CONTROL SYSTEM WITH TYPE SC15 FUSE OR FUSE LIMIT INPUT WITH TYPE SC5 FUSE RS 485 DDL CONNECTOR IS ON R7999 CONTROLLER MUST USE APPROVED FUEL SELECT SWITCH CENTER OFF POSITION NORMALLY OPEN MOMENTARY SWITCH CONNECTION BETWEEN TERMINALS 35 AND 38 MANUAL FIRING RATE POTENTI0MET...

Page 9: ... VOLTAGE TO CONTROL SYSTEM WITH TYPE SC15 FUSE OR FUSE LIMIT INPUT WITH TYPE SC5 FUSE RS 485 DDL CONNECTOR IS ON R7999 CONTROLLER MUST USE APPROVED FUEL SELECT SWITCH CENTER OFF POSITION NORMALLY OPEN MOMENTARY SWITCH CONNECTION BETWEEN TERMINALS 35 AND 38 MANUAL FIRING RATE POTENTI0METER CONNECTION BETWEEN TERMINALS 36 AND 38 120 VAC RELAY WITH NORMALLY CLOSED CONTACT WIRED INTO LINE FROM 7800 SU...

Page 10: ...ING RATE POTENTIOMETER CONNECTION BETWEEN TERMINALS 36 AND 38 AN EXTERNAL LINE VOLTAGE 120 VAC RELAY MUST BE ADDED AND WIRED AS SHOWN IN THE ADJACENT PICTURE THE EXTERNAL RELAY IS REQUIRED TO DELAY THE LFP INPUT TO CONTROLINKS SINCE THE FIREYE CONTROL POWERS BOTH THE LFP AND HFP AT THE SAME TIME CONTROLINKS DOES NOT ALLOW THIS CONDITION REMOVE THE LIMIT OPERATING SWITCHES INPUT FROM THE FIREYE TER...

Page 11: ...lay test failed Reset controla 24 Internal error Time storage Microprocessor test failure Reset control a 25 Internal error Limited move Actuator moving to a position during commissioning mode Reset control a c Check the feedback pot on the actuator indicated by the LED 26 Internal error Targeted move actuator moving to a position but not getting to the postions Reset control a c Can get this if y...

Page 12: ...r did not go to its commanded position Check for stuck air actuator and or proper shielding on actuator interface Try changing degree of accuracy to 0 5 degree 71 Verifies that the Air actuator accepted the offline online move counter clock wise and move clock wise commands Furthermore all potentiometer tests must be successfully passed to bring an actuator online Check wiring of actuator verify c...

Page 13: ...s as described in the ML instructions 4 You can now go back through the commission procedure to set up the new actuator by entering the serial number and establish the end points 5 Once entered you can download the existing curve and verify the curve firing points If the motor had been removed and is now added to the R7999 system the R7999 will lockout because the motor serial numbers won t match ...

Page 14: ...ter command on the Commission screen to enter the pass word You should be into the setup screen If the R7999 Alarms again you may need to repeat the above steps 5 You cannot enter ControLinks commissioning while it is in Alarm 6 Once you have entered the Commission screen return to the replaced actuator and reconnect the Red connec tor 7 Return to the commissioning process by entering the new actu...

Page 15: ...R7999A B CONTROLINKS CONTROLLER 15 65 0238 10 ...

Page 16: ...omation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 65 0238 10 M S Rev 02 13 Printed in United States ...

Reviews: