Appendix A - Installing RTP
l
SDC+ refers to switched positive side of the DC supply.
l
Terminals 9 and 11 (DC-) are connected through the RTP cable. Same for
terminals 10 and 12 (DC-).
Using an RTP to field wiring the 8 Point AC DO
ATTENTION:
l
RTP and cables are intended for permanent installation within their own
enclosure.
l
8 point AC Output is limited to maximum of 2A per output for any VAC, 6A
per RTP for 240VAC, 8A per RTP for 120VAC.
l
The RTP combines the 8 isolated outputs into one group of 8.
To wire the 8 Point AC DO using an RTP:
1. Mount the RTP cable assembly to ControlEdge 900 Controller. See the
following figure for the example installation diagram.
207
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...