LED Failure Definition
Number
of
strobes
Failure
Description
User Action
Applies
to
1
Failsafe
The module is in
the failsafe state
because it is not
receiving
message
requests from
the CPU or the
whole system is
in exception
stop.
1. If expansion I/O rack, go to step
2. If non expansion I/O rack, go
to step 3.
2. Check the Scanner status LED If
it’s flashing 6 times, proceed
with step 3. If it’s flashing some
other red status code, refer to
Table 29 to solve that problem
first. If it’s flashing green, the
module probably is not required
in the configuration. If it’s not on
or steady, cycle power to the
scanner.
3. Make sure the module is the
correct one for the
configuration.
4. Remove the module and check
for a bent pin, then reinsert the
module
5. Replace the module
6. Remove other modules and
replace one at a time until the
problem reoccurs. Most likely the
last module inserted needs to be
replaced.
7. Replace the rack.
All
modules
2
HW/SW
Key
The software
residing on the
module does
not match the
module type.
This diagnostic
should only
result in the
factory.
Replace module
DI and
Relay
DO and
DC DO
174
Chapter 8 - Diagnostics and Troubleshooting
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...