MODEL 50 CONTROLLER
–
INSTALLATION AND COMMISSIONING INSTRUCTIONS
31-00233-02
62
Figure 53: CIPer Model 50 RS232 / RJ45 socket
Table 25. RS232-to-PW cable specifications
RJ45 plug, pin no.
RS232 function
9-Pin sub-D connector pin no.
1
DCD
1
2
RxD
2
3
TxD
3
4
DTR
4
5
GND
5
6
DSR
6
7
RTS
7
8
CTS
8
--
Not used
9
Figure 54: YIOVVOM DB9 Breakout Connector power / communication cable details
Cabling PW3/PW20/PW60 to M-Bus
•
Use shielded, twisted pair cable 322 or 3251.
•
Shielding is especially recommended when the M-Bus cable is installed in areas with expected or actual
electromagnetic noise. Avoiding such areas is to be preferred.
•
Connect the shield to a noise-free earth ground
–
only once per M-Bus connection.
•
Power the CIPer Model 50 controller and the PW M-Bus Adapter with separate transformers
–
see
WARNING below.