Honeywell CIPer 30 Installation And Operation Manual Download Page 36

CIPer

TM 

MODEL 30 CONTROLLER - INSTALLATION AND OPERATIONS GUIDE 

31-00206 - 02 

36 

 

 

 

 

5.

 

Connect the platform and navigate to the TCP/IP Configuration option under Platform. 

6.

 

Double-click on TCP/IP Configuration. 

 

7.

 

Update the required fields, like default IP address. 

8.

 

Click 

Save 

to apply the changes. 

Serial  Communication  setup 

For serial communication, you can use software like 

Tera Term 

or 

PuTTY

. Serial communication allows 

you to perform following function. 

 

Reset to factory defaults. 

 

Use serial communication in case you forget the IP address you have configured for the CIPer 
30 controller. 

 

Reset switch configuration  to factory defaults. 

To connect the CIPer Model 

30 

controller using serial console: 

1.

 

Launch Tera Term application and open new connection window. 

2.

 

Select 

Serial 

option and select required port from the drop-down list. 

 

3.

 

Click 

OK 

4.

 

Select 

Serial port 

from Setup menu drop-down. This action takes you to the Serial port setup 

window. 

Summary of Contents for CIPer 30

Page 1: ...CIPerTM Model 30 Controller INSTALLATION AND OPERATIONS GUIDE July 2021 U S Registered Trademark Copyright 2021 Honeywell Inc All Rights Reserved 31 00206 02 ...

Page 2: ...ior written permission from Honeywell Copyright 2021 HONEYWELL International Inc All rights reserved Niagara Framework is a registered trademark of Tridium Inc Trademark Notice BACnet and ASHRAE are registered trademarks of American Society of Heating Refrigerating and Air Conditioning Engineers Microsoft Excel Internet Explorer Windows Windows Vista Windows Server and SQL Server are registered tr...

Page 3: ... to Upgrade CIPer Model 30 Controller and Expansion IO 12 Procedure 1 Distribution File Installer 12 Procedure 2 Using Commissioning Wizard 15 Procedure 3 Using Niagara Provisioning Service 19 Verify Upgrade 22 To Verify Baseboard Version 22 To Verify Expansion IO Baseboard Firmware Version 23 Launching Niagara N4 25 Launching Niagara N4 from desktop 25 Launching Niagara N4 from application folder...

Page 4: ...of the information in this guide readers should have some training or previous experience working with Honeywell WEBs controllers as well as Niagara 4 or Niagara AX software Other Related Documents CIPer 30 Expansion IO Installation Instruction 31 00319 CIPer 30 Expansion IO Product Data 31 00239 CIPer Model 30 Installation and Operation Guide 31 00206 CIPer Model 30 Installation Instruction 31 00...

Page 5: ... 2012 and Windows Server 2012 R2 Supported Operating Systems Table 1 Supported Operating Systems Operating Systems Niagara 4 7 Windows 7 32 bit Yes Windows 7 64 bit Yes Windows 8 1 64 bit Yes Windows 10 64 bit Yes For a detailed matrix of supported operating systems refer to the Niagara Central Knowledge Article Supported Operating Systems And Relational Database Servers For Niagara Installations ...

Page 6: ...un installation Software Release Bulletin contains all the information regarding last enhancement fixes and build versions of the software for the CIPer Model 30 controller Upgrading Licensing and Certificates You can install CIPer Model 30 controller license locally or from licensing server Note CIPer Model 30 controller shipped with pre installed license and certificates But if you perform the f...

Page 7: ...d when there is a local license database Import Honeywell IPC Honeywell Webs 4 7 licenses from the licensing server To import license from the licensing server in case there are no license present in the local files and databases When you select this option for importing license the application displays following window to restart the station Import one or more license from files a If you saved th...

Page 8: ...in the window displayed d Click Ok This completes licensing Import Honeywell license from the licensing server a If you have access to licensing server select Import Honeywell IPC Honeywell Webs 4 7 licensing form the licensing server option and click OK b Select Import option from bottom of the certificate section ...

Page 9: ...CIPerTM MODEL 30 CONTROLLER INSTALLATION AND OPERATIONS GUIDE 9 31 00206 02 c Click Next d Click OK This completes licensing from licensing server ...

Page 10: ...from the local license database a Select the certificate file from the directory and click OK Installer displays import status of license and certificates Note After you completed installation of license and certificates for CIPer 30 controller Restart the workbench this will apply all the updates ...

Page 11: ...C0 html o Staged roll out module docModuleSign doc StagedRoll outModuleSigning 182E7CC0 html o Verification modes module docModuleSign doc VerificationModesModuleSigning 182D0E86 html If you attempt to upgrade an existing CIPer Model 30 controller with an unsigned module the station will not start For users using WEBs N4 8 version in CIPer Model 30 controller While installing any other tool packag...

Page 12: ...0 1 1 257 IPC Module honeywell IPC module dist 4 10 0 154 Niagara Core Software nre core honeywell IPCQNX arm dist 4 10 0 154 4 Niagara Config Software nre config honeywell IPC dist 4 10 0 154 6 NOTE Factory Reset Image The honeywell IPC factory dist file can be used to reset the CIPer Model 30 Controller to factory settings To install the honeywell IPC factory dist file use Distribution file inst...

Page 13: ...ing only controller tool use honeywell IPCtool 4 10 0 1 1 257 dist file for installation For upgrading controller baseboard firmware use honeywell IPCBASE dist 1 1 1 146 dist file for installation For upgrading large expansion IO firmware use honeywell IPCIO 1 1 0 140 dist file for installation For upgrading small expansion IO firmware use honeywell IPCIO 1 1 0 76 dist file for installation ...

Page 14: ...lder containing dist file from the C Honeywell WEBStation N4 4 10 0 154 sw 4 10 0 154 6 directory select the folder and select OK 3 Select the required dist file and click Install this action installs the dist file NOTE After this step the controller automatically stops and reboots the station ...

Page 15: ...E dist 1 1 1 146 OS QNX honeywell IPCQNX dist 7 0 4 4 JRE honeywell azul ejre ipcqnx arm dist 1 8 0 282 IPC Tools honeywell IPC tool dist 4 10 0 1 1 257 IPC Module honeywell IPC module dist 4 10 0 154 Niagara Core Software nre core honeywell IPCQNX arm dist 4 10 0 154 4 Niagara Config Software nre config honeywell IPC dist 4 10 0 154 6 Steps To Perform Commissioning Wizard 1 Log in to the Platform...

Page 16: ...TROLLER INSTALLATION AND OPERATIONS GUIDE 31 00206 02 16 4 Uncheck all default checkboxes except Install Upgrade core software from distribution files see below and click Next 5 Select the licensing options and click Next ...

Page 17: ...e from the distribution file should look like the below image If not then go back and make sure the files from the zip folder were copied to the correct location and that the WEBs N4 4 9 0 198 workbench was restarted NOTE DO NOT click the Upgrade All Out of Date during the Install Upgrade core modules step refer below image ...

Page 18: ...ON AND OPERATIONS GUIDE 31 00206 02 18 8 Click Next and complete the commissioning wizard Wait for several minutes to complete the controller upgrade After the upgrade is complete you will be able to log in to the platform of the controller ...

Page 19: ...g service allows you to upgrade multiple CIPer Model 30 controllers and Expansion IO For additional information on setting up provisioning service see the CIPer Model 30 Installation and Operation Guide 31 00183 or open the following ORD local module docProvisioning doc ProvisioningInstall html on your workbench NOTE Installing the honeywell IPC factory dist file is not possible by Provisioning Se...

Page 20: ...k the icon from Steps run for each station section select Upgrade Out of date Software and then click OK You can view the list of jobs defined for the required stations 3 Click the icon from Stations to include in the job section select the checkbox to select a specific station or select the Check All option to select the all listed station and then click OK NOTE Make sure to increase the Device R...

Page 21: ...CIPerTM MODEL 30 CONTROLLER INSTALLATION AND OPERATIONS GUIDE 21 31 00206 02 4 Click Run Now This upgrades CIPer Model 30 controller and Expansion IO to WEBs N4 10 version for all selected stations ...

Page 22: ...To Verify Baseboard Version 1 Go to Application Director and start the station Wait for the station to start when the station status displays running 2 Log in to the station If you are logging into the station the first time then use default credentials Username admin Password Honeywell1 The change password wizard will come up to change the default credentials 3 Navigate to Station Drivers IPCNetw...

Page 23: ... Station Drivers IPCNetwork and click on localDevice 2 Drag the Large Expansion IO device from the ipcProgrammingTool palette and configure the model type as WEBO9056H and the address to what is configured on the DIP switches of the expansion IO module Make sure that the status shows OK and the firmware version shows 1 1 0 140 as seen below ...

Page 24: ...om the ipcProgrammingTool palette and configure the model type as WEBO3022H and the address to what is configured on the DIP switches of the expansion IO module Make sure that the status shows OK and the firmware version shows 1 1 0 76 as seen below This completes the CIPer Model 30 WEBs N4 10 version upgrade process ...

Page 25: ...llowing steps if you have more than one version of Niagara installed on your computer to make sure the right Niagara daemon is running 3 Right click the console in the Niagara bin folder and click Run as Administrator 4 On Administrator Niagara Command Line window run the command plat installdaemon and press the Enter key The daemon is installed and started 5 Enter wb and press the Enter key to st...

Page 26: ...to WEBStation N4 4 7 app from taskbar app list 2 Expand the WEBStation N4 4 7 folder 3 Run Install Platform Daemon and wait till the Install Platform Daemon window displays the successful installation of the platform daemon 4 Repeat the step 1 and step 2 and run WEBStation N4 Workbench This action launch Niagara workbench ...

Page 27: ... you can start configuring the controller with the WEBStation Connect all the required cables to the controller as shown in the figure Cable connections 1 Power Cables 2 Ethernet Cable 3 Serial Communication Cable Left Side view of the CIPer Model 30 controller Ports Details 1 Ethernet Ports 1 to 4 2 Serial Communication Port 5 Right Side view of the CIPer Model 30 controller 1 2 3 4 5 ...

Page 28: ...ult IP address 192 168 1 160 Default username honeywell Default password webs Default station username admin Default station password Honeywell1 Passphrase webs Note The CIPer Model 30 controllers come within built DIP Switch feature before configuring IP setting make sure all DIP switches are in off position ...

Page 29: ...ntials Configure platform 1 Start the Niagara N4 x workbench 2 Connect to the CIPer Model 30 programming tool platform with default platform credentials and the default IP address and click OK 3 Verify the certificate details displayed during the connection establishment and click Accept This action display Authentication Window 4 Enter default platform credentials in the Authentication window and...

Page 30: ...06 02 30 5 Click Next to continue Change Platform Defaults Wizard The Change Platform Defaults Wizard also lets you configure the system passphrase creating a new platform account and remove the default platform account 6 Enter and confirm the new passphrase click Next ...

Page 31: ...TION AND OPERATIONS GUIDE 31 31 00206 02 7 Enter a New Username New Password and Confirm Password to create the new platform and then click Next to continue 8 Click Finish to complete the platform setup This action launch Platform screen ...

Page 32: ...ONTROLLER INSTALLATION AND OPERATIONS GUIDE 31 00206 02 32 9 Open the Application Director by double clicking the Application Director option on the Platform screen You can also launch Application Director from nav tree ...

Page 33: ...tion click Start from the right side of Application Director window Note Auto Start option has been disabled because of security reason 2 Double click the default station after successful starting the station 3 Verify the certificate details displayed during the connection establishment and click Accept to continue ...

Page 34: ...e default station credentials in the Authentication window and then click OK to continue This action display Reset Password window Default station username admin Default station password Honeywell1 5 Enter and confirm the password for the new station to be created and click OK to continue ...

Page 35: ... the CIPer Model 30 controller to the system 2 Open Network Connections under Control Panel and double click Ethernet to set up the IP address for computer Note Set the IP address of workstation and controller in same series example 192 168 1 XXX so that controller and workstation can communicate Also Controller IP address should be unique i e controller and workstation IP address should not match...

Page 36: ...Tera Term or PuTTY Serial communication allows you to perform following function Reset to factory defaults Use serial communication in case you forget the IP address you have configured for the CIPer 30 controller Reset switch configuration to factory defaults To connect the CIPer Model 30 controller using serial console 1 Launch Tera Term application and open new connection window 2 Select Serial...

Page 37: ...you forget the station credentials you can reset to the factory defaults Follow the below steps to reset CIPer 30 controller to default factory setting Since this operation is performed in bootloader the controller must be running in bootloader 1 Connect the CIPer 30 controller with serial console using terminal emulators tool for example Putty Note The default baud rate of the CIPer Model 30 cont...

Page 38: ...le the device 2 When system displays Hit any key to stop autoboot type passphrase enters and press Enter key on the keyboard Note Complete the step 3 within 5 seconds If fail to enter system will continue autoboot This action redirects you to factory reset menu and conformation message is displayed Are you sure to reset to factory defaults Y N ...

Page 39: ... Enter key on the keyboard this action reset controller to default factory settings Wait until the LED shows the device is working properly Do not power off the controller during the reset process or the controller will be damaged permanently This completes CIPer Model 30 Controller factory reset ...

Page 40: ...tem Engineering User Guide 31 00236 Configuring RSTP via Workbench 1 Open the Niagara workbench 2 Connect to the required platform and station 3 Navigate to IPCNetwork folder under Station Config Drivers expand IPCNetwork 4 Double click on Local Device and select RSTP Configuration 5 Select true to Enable the RSTP communication 6 Select true to run Reboot After Save function This function reboots ...

Page 41: ...ied range 10 Click Save to apply the changes or select Refresh to cancel the changes 11 Right click on the RSTP workbench window click Action Apply RSTP settings This action reboots the controller and effected changes will be effective Honeywell Building Technologies Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2020 Hon...

Reviews: