background image

X-XX UL

INSTALLATION INSTRUCTIONS

69-0309-9

T8602A,B,C,D and TS8602A,C

Chronotherm

®

 III Fuel Saver Thermostats

APPLICATION

These thermostats provide energy saving control for
24 Vac conventional heating/cooling system or 750 mV
heating and 24 Vac cooling as indicated in Table 1.

Power is supplied for the device by three AA alkaline
batteries (included). This allows the thermostat to be com-
patible with all control applications.

Cycle rates are adjustable for heating.

The TS8602 current rating in heating is 0.1A at 750 mV.
The current rating on all other models is 1.6A maximum,
up to 30 Vac.

Adaptive Intelligent Recovery™/Conventional Recovery
selection screw is included on the back of the thermostat.

Fan operation switch is included on the back of some
T8602C models to select either independent or direct
thermostat control of the fan in heating.

12/24 hour clock conversion and 

°

C/

°

F conversion are

available on some models only.

RECYCLING NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do 

not place your old

control in the trash. Contact your local waste
management authority for instructions regarding
recycling and the proper disposal of your old
control.

If you have any questions, call Honeywell Inc.
at 1-800-468-1502.

INSTALLATION

When Installing This Product…

1

Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.

2

Check the ratings given on the product to make sure
the product is suitable for your application.

3

Installer must be a trained, experienced service
technician.

4

After installation is complete, check out product
operation as provided in these instructions.

5

Allow thermostat to warm to room temperature
before operating.

Table 1. Thermostat Models.

Stages

Switching

Thermostat

Heat

Cool

System

Fan

Application

T8602A

1

Gas, oil or electric with independently
controlled fan.

T8602B

1

ON-AUTO

T8602B

1

HEAT-OFF

T8602C

1

1

HEAT-OFF-COOL

ON-AUTO

T8602D

1

1

HEAT-OFF-COOL-AUTO

ON-AUTO

T8602C

1

1

HEAT-OFF-COOL

ON-AUTO

Fan operation in heating selectable for

thermostat or independent control; with O
and B terminals for changeover control.

TS8602A

1

Millivolt heating system.

TS8602C

a

1

1

HEAT-OFF-COOL

ON-AUTO

Millivolt heating and 24 Vac cooling

system.

a

Available only in Canada.

®U.S. Registered Trademark
Copyright © 1995 Honeywell Inc.  •            •   All Rights Reserved

Summary of Contents for Chronotherm III T8602A

Page 1: ...ocal waste management authority for instructions regarding recycling and the proper disposal of your old control If you have any questions call Honeywell Inc at 1 800 468 1502 INSTALLATION When Installing This Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given on the product to make sure the product ...

Page 2: ...late does not require leveling for operation but for appearance only The wallplate mounts directly onto the wall with the screws included Using the wallplate as a template with a pencil mark two of three mounting screw positions on the wallplate that fit the application See Fig 2 Use a 3 16 in bit to drill holes for the anchors Gently tap anchors into the holes until flush with the wall surface Th...

Page 3: ...in an oil system L1 HOT L2 1 W R HEATING ONLY WALLPLATE 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M2923 RESISTANCE HEATER SWITCH HEATER BLACK BLUE RED RED WHITE R841C BIMETAL SWITCH Fig 8 T8602A B heating only circuit in an electric baseboard or ceiling cable system Fig 3 Keep wiring restricted to the ribbed area surrounding terminals W MILLIVOLT HEATING ONLY WALL...

Page 4: ...ION AIR BLOWER MOTOR COMBUSTION AIR BLOWER RELAY AIR PROVING SWITCH W R Fig 9 T8602A B heating only circuit in a Honeywell Intermittent Pilot Gas Burner Ignition System L1 HOT L2 1 C W Y R G W R W R W R W R ZONE 1 HEATING ONLY WALLPLATE ZONE 2 HEATING ONLY WALLPLATE ZONE 3 HEATING ONLY WALLPLATE ZONE 4 HEATING ONLY WALLPLATE 2 3 3 3 3 R8239A1052 R8222B1067 R8222B1067 R8222B1067 1 POWER SUPPLY PROV...

Page 5: ... PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PRIMARY CONTROL SUCH AS GAS VALVE OR ELECTRONIC IGNITION MODULE CURRENT DRAW FOR W OR Y PLUS G MUST BE LESS THAN 1 6A M2924 W G HEATING COOLING WALLPLATE R RC Y COOLING CONTACTOR FAN RELAY HEATING PRIMARY CONTROL L1 HOT L2 1 L1 HOT L2 1 1 2 3 3 2 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PRIMARY CONTROL...

Page 6: ...CTORY SETTING IN IN TIME TEMP DISPLAY 2A 2B 24 HR IN 12 HR o o C F OUT 1 2 TO 1 TURN OUT 1 2 TO 1 TURN IN RECOVERY SELECTION ADAPTIVE INTELLIGENT CONVENTIONAL 3A IN FACTORY SETTING OUT 1 2 TO 1 TURN M2082C 1 SCREWS 2A 2B AVAILABLE ON SOME MODELS ONLY 2 SWITCH 4A FOR FAN OPERATION SELECTION AVAILABLE ON SOME MODELS ONLY 1 3A 1A 1B 2A 2B 4A 2 Fig 16 Cycle rate adjustment SETTINGAND ADJUSTMENTS Adjus...

Page 7: ...mostat from the wall and install three new AA alkaline batteries We recommend Energizer batteries Change batteries within approximately 30 seconds from the time the batteries are removed to prevent program loss and the necessity to reprogram IMPORTANT The low battery warning will be displayed about two months before the batteries are dead When the batteries are dead the system will shut down After...

Page 8: ...system switch to COOL and the fan switch to AUTO Press COOLER key until the setting is about 10 F 6 C below room temperature The cooling equipment and fan should start Press the WARMER key until the setting is about 10 F 6 C above room temperature The cooling equipment and fan should stop NOTE On an AUTO changeover thermostat T8602D the heating temperature must be set at least 3 F 2 C below the co...

Page 9: ...e fan switch is in AUTO A HEAT displayed when system switch is in HEAT COOL when in COOL HEAT and COOL when in AUTO neither when in OFF Also a four digit code is displayed with each digit explained as follows m 1 m A This equipment is a Class B digital apparatus which complies with Canadian Radio Interference Regulations CRC c 1374 First Digit Cycle Rate Setting cph At 50 On Time 0 or 1 1 2 or 3 3...

Page 10: ...69 0309 9 10 T8602A B C D AND TS8602A C Chronotherm III FUEL SAVER THERMOSTATS ...

Page 11: ...69 0309 9 11 T8602A B C D AND TS8602A C Chronotherm III FUEL SAVER THERMOSTATS ...

Page 12: ... and Building Control Honeywell Limited Honeywell Limitée 740 Ellesmere Road Scarborough Ontario M1P 2V9 Helping You Control Your World 69 0309 9 J H Rev 7 95 Printed in Taiwan R O C QUALITY IS KEY Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 ...

Reviews: