CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
54
CGW-MB Control Features
Modbus Communications
7.19.2 Enabling the Control
CGW-MB control is enabled through a web page-based configuration tool running on the
CLSS Gateway mainboard. Enable control as follows:
1. Start the web browser on a computer that is in the same IP network as the CGW-
MB.
Note
: Chrome is the recommended browser.
2. Enter the following URL in the browser:
https://192.168.10.190:9443/config/index.html
3. Do the following if any security warning is shown. Otherwise, go to step 4.
• Click the
Advanced
link below the error message.
• Agree to proceed.
4. In the
CLSS Gateway mainboard Configuration Tool
page, enter the password.
5. Go to
Modbus Tools
in
Modbus Settings
.
6. Enable or disable as needed in the control functionality.
7. Read the
UL Void
message shown, if it is enabled.
8. Click
Save
.
9. Wait until the CGW-MB shows the changes.
10.Check that the changes are correct.
7.19.3 Control Commands
Using the CGW-MB you can send relevant command values to the holding registers of
Points, Panels, and Zones.
Point Commands
Panel Commands
CAUTION: UL LISTING
ENABLING CONTROL VOIDS THE UL LISTING OF THE CGW-MB.
NOTE:
section for detailed register mapping information.
Serial
No.
Command
Value
Holding Register
1
EnableDisableDevice
0x400 - Enable
Use Device/Module Holding Register
Address
2
EnableDisableDevice
0x500 - Disable
Use Device/Module Holding Register
Address
Serial
No.
Command
Lower Byte value
Holding
Register
1
System Reset
0x0000
20001
2
Signal Silence
0x0001
20001
3
Deactivate Buzzer
0xE
20001
4
Walk Test Sounder on
0xF
20001
5
Walk Test no sounder on
0x10
20001
6
Walk test off
0x11
20001