CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
17
CLSS Gateway mainboard Board Layout
Overview
2.3.2 LED Indicators
The LED indicators on the CLSS Gateway mainboard board use different colors to
identify the operational status of the CLSS Gateway mainboard. To know the location of
the LED indicators on the CLSS Gateway mainboard board, refer to
Figure 2.2: The LED Indicators on the CLSS Gateway mainboard
Table 2.2: LED Indicators and Their Messages
SOM
Power-Indicating LED
Indicates the CLSS Gateway mainboard board’s received power status. See “Power
.
ON
The circuit board is receiving 24V power from its power source.
OFF
The circuit board is
not
receiving power.
DL1
LTE Power LED
Indicates the power supply status for cellular communications
ON
The LTE radio device is receiving power from the circuit board.
OFF
The LTE radio device is
not
receiving power.
DL2
Trouble LED
Indicates the CLSS Gateway mainboard’s operational status
OFF
There are no issues.
FLASHING SLOW
(flashes once per 1 second) There are communication
issues with the panel or the Internet connectivity.
ON
There is a critical error in the system.
To fix the issues, you can refer to the
section, which
discusses about some possible issues and their solutions.
DL6
Mobile Connectivity LED
Indicates the status of mobile communications between the CLSS Gateway
mainboard and the CLSS App.
FLASHING SLOW
(flashes once per 1 second) The CLSS Gateway
mainboard is connected to the CLSS App.
FLASHING FAST
(flashes once per 0.25 second) The CLSS Gateway
mainboard is ready for the CLSS App connection.
OFF