I/O Initialization
Inputs
Outputs
Values
Pulse Converter
Reference
Inputs
Initialization
(
Initial
value)
´0`. Continued
with value
transmitted from
field device
´Relinquish
default`. With first
heartbeat,
´Relinquish default`
or application value
is sent to LON bus.
Manual Override
switch is read from
LON module
´Relinquish
default`.
´Start value`
defined in CARE.
Continued with
referencing input
value.
Alarming
After start alarm
time has
expired, alarm is
saved in the
alarm buffer,
shown in the
alarm list and
reported to the
EBI as long as
the alarm exists.
After start alarm
time has expired,
alarm is saved in
the alarm buffer,
shown in the alarm
list and reported to
the EBI as long as
the alarm exists.
After start alarm
time has
expired, alarm is
saved in the
alarm buffer,
shown in the
alarm list and
reported to the
EBI as long as
the alarm exists.
Battery-retentive
RAM Storage /
Restorage after
Restart, Reset,
Power Failure
Runtime
Counter
Last reset time
Elapsed active
time
Out of Service
Manual value
Runtime Counter
Last reset time
Elapsed active time
Value with highest
BACnet array
priority (2 – 8),
includes Manual
value
Last reset time
Elapsed active
time
Value with
highest BACnet
array priority (2
– 8), includes
Manual value
Count value
Reset time
Manual Override
Value saved in
battery-retentive
RAM
Saved in the
battery-retentive
RAM
Saved in the
battery-retentive
RAM
Setting Datapoints into Manual Mode (Manual Override)
A datapoint´s current value can be overridden manually either by:
•
Entering the manual value in the datapoint´s dialog box in the Excel Web HTML
Interface or EBI central (applies to all datapoints). This is often called “fixing a
point”
Or,
•
Using manual override controls on the analog output (XFL522) or digital output
(XFL524) modules (applies to analog and binary output datatpoints only).
See also "Feedback Value" section.
NOTE: If AO and BO datapoints are created with switches, the manual override
control of the modules are reflected in the command priorities (level 1 =
manual life safety).
NOTE: Switching a point between Auto and Manu operating mode only causes an
alarm if the value or state is in the Off-Normal range or status, and if the
alarming is enabled.
Setting and Detecting Manual Overrides of Analog, Binary, and Multi-State Outputs
Procedure
1.
In the
Details
dialog box of the selected datapoint, select the
Values
tab.
Summary of Contents for Centraline FALCON
Page 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Page 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Page 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Page 9: ......
Page 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Page 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Page 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Page 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...