USER GUIDE
FALCON
71
EN2Z-0962GE51 R0715
A user who has a user level equal to or higher than the assigned write access level
of the datapoint, will have this access right enabled in the Excel Web HTML
Interface, all others will not (for further details, please refer to the User
Administration section).
Datapoint Properties Overview
Each point in a controller has associated properties such as datapoint name,
notification class and descriptor. Point properties may not be available for editing in
BACnet front-ends such as the EBI central, or in the Excel Web HTML Interface.
Contrariwise in CAREm, some online properties such as present value, statuses,
etc. are not available in principle.
This chapter contains tables for each point type. The tables list point properties and
presents the following information for each:
•
Property denotation
specifies either the attribute name in the related CARE
Datapoint Properties
tab and/or in the Excel Web
Datapoint Details
tabs.
•
Whether or not the property is available for
off-line editing
. “Off-line” editing
refers to changes made to database values while the controller is not active in
the system. In other words, when you are using CARE to change copies of
controller files, not the files in the actual controller.
•
Whether or not the attribute is available for
on-line editing
. “On-line” editing
refers to changes made to controller files while the controller is active. For
example, if you are using the Excel Web HTML Interface or a BACnet client to
change field values in a controller while it is operating.
Analog Input
Property Denotation
Online-Editing
Offline-Editing
Excel Web HTML
Interface
CARE
BACnet
Excel Web
HTML Interface
BACnet
CARE
"Datapoint name displayed
in title line of dialog"
Datapoint Name
-
+
GENERAL
Description
Descriptor
description
-
+
+
Type
“datapoint type”
“n.a.”
-
-
Mapping
“n.a.”
-
-
NV Name
"automatically
generated by
CARE"
-
-
NV type
Input NV
-
+
NV type
Output NV
-
+
Direction
Lon Point
-
+
Read access level
Read access level
-
+
Write access level
Write access level
-
+
ALARMING
Notification class
Notification class
notification-class
-
+
+
Notify type
Notify type
notify-type
-
+
+
Event:
To Off-Normal, To Fault,
Back to Normal
“selectable
under Reporting, see
Reporting:
To Off-Normal, To
Fault, Back to
Normal
+
+
Summary of Contents for Centraline FALCON
Page 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Page 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Page 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Page 9: ......
Page 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Page 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Page 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Page 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...