FALCON
USER GUIDE
EN2Z-0962GE51 R0715
70
Time of Last Reset
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
Equivalent
Shows the time of the last reset of a binary output or pulse converter datapoint.
Transition Events
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
"see Reporting"
x
Equivalent
Event
Defines which transition type (To-Off-Normal, Back To-Normal, and/or To Fault) will
be reported and tracked by time stamping. The timestamps can be seen in the Excel
Web HTML Interface.
See also "Event" and "Reporting" sections.
Type
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
Equivalent
Shows the datapoint type, e.g. analog input, digital output, etc.
With Switches / 3 Position Output
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
x
Equivalent
The With Switches / 3 Position Output options are not visible in the Excel Web
HTML Interface, but only in CARE.
Defines whether the point transmites a continuous signal and is on a board with
switches (AO, BO), or if the point is a 3 position output (AO).
Write Access Level
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
x
Equivalent
The write access level can be defined and changed in CARE only. In the Excel Web
HTML Interface, the write access level is displayed only.
The write access level assigned to a datapoint determines which user level can write
values (properties) to that particular datapoint on the Excel Web HTML Interface.
Summary of Contents for Centraline FALCON
Page 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Page 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Page 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Page 9: ......
Page 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Page 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Page 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Page 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...