The read access level can be defined and changed in CARE only. In the Excel Web
HTML Interface, the read access level is displayed only.
The read access level assigned to a datapoint determines which user level can read
values (properties) of that particular datapoint on the Excel Web HTML Interface.
A user who has a user level equal to or higher than the assigned read access level
of the datapoint, will have this access right enabled in the Excel Web HTML
Interface, all others will not (for further details, please refer to the User
Administration section).
Reference
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
x
Equivalent
The reference property of a reference input point provides the source (BACnet
object) which passes the value to the reference input point. The reference property
of a reference output point provides the source (BACnet object) which passes the
value to the reference output point.
Sources can be any point of any Excel Web controller and 3
rd
-party BACnet device
of the project.
Reference Points
Reference points are a type of software point that can share point information
across plants. If plants are located in different controllers, the point information will
be automatically transferred across the BACnet bus.
Reference Input Points
Reference input points receive information from a point in another plant of the same
controller (internal reference) or of another plant in another controller or 3
rd
- party
device (external reference). Controllers and 3
rd
- party devices can reside in the
same or in different projects (for detailed procedure see CARE User Guide EN2B-
0182GE51).
Each reference input is associated with a physical or value datapoint (source point)
somewhere in a plant residing in a controller on the bus. The source point cannot be
a receiver point and source point and receiver point cannot reside in the same plant.
BACnet-Bus
Plant A1
Source Point
Plant A2
Receiver Point
Physical Point or
Value Point
Reference
Input Point
CONTROLLER A
Data
Data
Plant B1
Source Point
Physical Point or
Value Point
CONTROLLER B / 3rd Party DEVICE
NOTE:
Controllers / 3rd Pary Devices can be in the same or in different projects.
Fig. 14. Data exchange between plants via reference input points
Summary of Contents for Centraline FALCON
Page 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Page 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Page 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Page 9: ......
Page 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Page 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Page 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Page 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...