FALCON
USER GUIDE
EN2Z-0962GE51 R0715
186
•
Direction
Shows the type of direction, input or output NV, e.g. NV in
Access Rights
Shows the read and write access level of the datapoint.
To write values to a datapoint, you must have a write access level equal or
higher than the write access level of the datapoint.
Datapoint details will only be displayed if you have a read access level equal to
or higher than the read access level of the datapoint.
2.
Click the SUBMIT button to save settings.
3.
To view /edit alarming details, click on the
Alarming
tab (see "View / Edit
Alarming" section.
View / Edit Alarming
Procedure
1.
In the
Details
dialog box of the selected datapoint, select the
Alarming
tab.
Here you can enable/disable alarm reporting and Off-Normal conditions and
view alarm information such as the notification class and alarm type.
Intrinsic Reporting
Intrinsic Reporting means, that only the present value property is to be
considered for alarming.
•
Notification Class
Shows the name of the notification class. The value in brackets is the
BACnet object ID of the notification class.
•
Alarm Type
By default all alarms are of the type ´event`.
•
Transitions
Here the following data about transitions are shown:
Summary of Contents for Centraline FALCON
Page 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Page 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Page 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Page 9: ......
Page 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Page 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Page 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Page 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...