USER GUIDE
FALCON
EN2Z-0962GE51 R0715
11
SYSTEM OVERVIEW
General
The Excel Web® is a BACnet/IP-based, freely programmable building automation
controller.
Excel Web® incorporates the two major open standards in building automation:
BACnet® and L
ON
W
ORKS
®.
As a native BACnet® building controller, Excel Web® integrates into any 3
rd
-party
BACnet® system and can integrate 3
rd
party BACnet devices and controllers.
Furthermore, Excel Web® is a full L
ON
W
ORKS
® controller. This gives the benefit of
enabling you to use of Honeywell’s complete L
ON
W
ORKS
® product portfolio and 3
rd
-
party LON products.
The Excel Web® can host a huge variety of building management applications, be it
traditional heating, ventilation, and air conditioning (HVAC) applications, energy
management functions, including optimum start/stop, night purge, and maximum
load demand, supervisory functions for lighting, sunblind, heat and energy metering
and many other applications.
By virtue of its "peer-to-peer" concept, Excel Web® is not dependent upon the
availability of super ordinate centrals or application network controllers.
Excel Web® seamlessly integrates into Honeywell’s Enterprise Buildings
Integrator™ (EBI) and SymmetrE® front-ends.
Versions and Firmware
Excel Web Versions
XL1000B50 / XL1000C50
52 physical datapoints and 50 Schedule Objects, 128 trend objects
XL1000B100 / XL1000C100
104 physical Datapoints and 50 Schedule Objects, 128 trend objects
XL1000B500 / XL1000C500
300 physical Datapoints and 50 Schedule Objects, 128 trend objects
XL1000B1000 / XL1000C1000
600 physical Datapoints and 100 Schedule Objects, 128 trend objects
For more details such as RAM size, please refer to Product Data EN0443-GE51.
Excel Web Firmware
Linux operating system
XLWebExe-H-MM-LL.xwa, including firmware itself, BACnet driver and HTML pages
(H-MM-LL are version numbers).
Updating Firmware
If, at some later point in time, i.e. after the release of a new version of the firmware,
the user wishes to download the new firmware into the Excel Web, this can be done
either via USB or Ethernet, using the CARE.
Browser Access / Operater Interface
Operator Interface
The Excel Web® is operated via a standard web browser (Excel Web HTML
Interface). By default, an integrated web server provides all operation pages for a
full browser-based operation. Through the consequent use of software standards,
any PC platform can be used as an operator interface (client). In addition to laptops
and desktop PCs, panel PCs can also be used for direct flush mounting into panel
doors. Other than the operating system and Internet Explorer® or Netscape®, no
software needs to be installed on the client PCs.
Alternatively – or in addition – Excel Web can be operated with the Excel Touch
operator interface, which is a 5.7” touch-screen device (order number “XI882” For
Summary of Contents for Centraline FALCON
Page 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Page 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Page 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Page 9: ......
Page 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Page 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Page 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Page 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...