Recommendation
Set the high and/or low limits to extremely high or low values, so that a real
measured value will not be above the limits.
Always enable the High limit Enable and Low Limit Enable options even if the Off-
Normal Reporting is disabled.
Analog Input
The following diagram shows the alarm behavior of an analog input.
Fig. 17. Alarm behavior of analog input datapoint
Analog Output
The following diagram shows the alarm behavior of an analog output.