APPLICATION

The C7189 Wall Mount Temperature Sensor provides the
input required by the PC8900 Perfect Climate® Comfort
Center with the W8900 Remote Module to sense tempera-
ture in indoor air spaces.

SPECIFICATIONS

Operating Ambient Temperature Range:
40 to 95

°

F (4.4

°

C to 35

°

C)

Humidity Setting Range:
None

Operating Relative Humidity:
5% to 95% noncondensing

Finish:
White

Dimensions in Inches (millimeters):
2 3/4 (70) width x 4 5/8 (117) height x 1 1/16 (27) depth

Accessories:
202689A Mounting Plate Assembly used to cover marks

left on the wall by the old thermostat

INSTALLATION

When Installing this Product...

Read these instructions carefully. Failure to follow

them could damage the product or cause a hazard-
ous condition.

Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

Installer must be a trained, experienced service

technician.

After installation is complete, check out product

operation as provided in these instructions.

CAUTION

Disconnect power supply before connecting wiring
to prevent electrical shock or equipment damage.

Location and Mounting

Locate the C7189 Wall Mount Temperature Sensor where
the setting will not be subjected to tampering.

Choose a location for the sensor on an inside wall

about 5 ft (1.5 m) above the floor. A horizontally
mounted standard 2 x 4 in. (51 x 102 mm) junction
box can also be used at the selected location for the
C7189.

Be sure that the wire distance between the C7189

and the W8900 does not exceed 200 feet.

Make sure that there is good air circulation at

average temperature at the chosen location. Avoid
the following locations because they can introduce
errors in sensor measurements. See Fig. 1:

Hot areas caused by:

• Concealed pipes or ducts.
• Drafts from fireplaces or other heat sources.
• Convection or radiant heat from the sun or

electrical equipment.

Cold areas caused by:

• Concealed pipes or ducts.
• Drafts from windows and doors.
• Unheated areas on the other side of the wall

location.

Dead air areas:

• Behind doors, furniture and curtains.
• In corners and alcoves.

Mark the area on the wall where the C7189 Sensor

or junction box will be mounted.

69-0895-1

Summary of Contents for C7189A

Page 1: ...tallation is complete check out product operation as provided in these instructions CAUTION Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage Location and Mounting Locate the C7189 Wall Mount Temperature Sensor where the setting will not be subjected to tampering 1 Choose a location for the sensor on an inside wall about 5 ft 1 5 m above the floor A h...

Page 2: ... not possible Ground the shielded cable to the GND terminal on the W8900 Important Erratic temperature readings from a sensor can occur as a result of any of the wiring practices described below These practices must be avoided to assure proper operation Use shielded cable to reduce interference if rerouting of sensor wiring is not possible a Do not route temperature sensor wiring with building pow...

Page 3: ...IRED GROUND TO GND TERMINAL ON W8900 GND C R RH RC C7189 W8900 S1 S S1 S Fig 2 Wiring Diagram for the C7189 Sensor to the W8900 Remote Module OPERATION The C7189 Wall Mount Temperature Sensor converts room temperature to a resistance that the controller can interpret The C7189 has a negative temperature coeffi cient NTC which means that the resistance decreases as the temperature increases Fig 3 s...

Page 4: ... recalibrated in the field Home and Building Control Honeywell Inc 1985 Douglas Drive Golden Valley MN 55422 Fig 3 C7189 Sensor Resistance vs Temperature Performance Characteristics OHM RESISTANCE F C M6357 RESISTANCE DECREASES 18 6 OHMS PER 1 F CHANGE OR 33 4 OHMS PER 1 C CHANGE 1 1 2000 2100 1900 1500 1600 1700 1800 1400 TEMPERATURE 40 4 50 10 60 16 70 21 80 27 90 32 100 38 1300 1000 1200 2200 2...

Reviews: