C7110C1001A / C7110D1009A 

WALL MODULES 

 

HONEYWELL EXCEL 5000 OPEN SYSTEM

 

PRODUCT DATA 

 

GENERAL 

The C7110C1001A and C7110D1009A are combined CO

2

 / 

temperature wall modules designed for applications in indoor 
ventilation and air conditioning systems. In conjunction with 
the Honeywell's Excel 5000 controllers, they can be used to 
control the flow of incoming fresh air, thus improving air 
quality while reducing energy consumption. During high-
occupancy periods, fresh air can be supplied to rooms in 
order to maintain acceptable air quality, while during low-
occupancy periods, the unnecessary conditioning of outdoor 
air can be avoided or reduced. 
 

FEATURES 

 

Fully compatible with the Excel 5000 controllers. 

 

CO

2

 sensor employing state-of-the-art Non-Dispersion 

Infrared (NDIR) technology. 

 

Selectable CO

2

 measurement range of 400…2000/3000 

ppm. 

 

Self-calibrating: automatic drift correction (ABC 
algorithm) based on long-term evaluation. 

 

External LED (C7110C1001A: CO

2

 level indication; 

C7110D1009A: auxiliary) 

 

Internal Service LED (visible after removing cover and 
setpoint wheel). 

 

MODELS 

order no. 

description 

C7110C1001A 

 0…10 VDC CO

2

 sensor output 

 0…10 VDC temperature output 

 CO

2

 level indication LED 

 Service LED 

C7110D1009A 

 0…10 VDC CO

2

 sensor output 

 NTC20k

 temp. sensor (passive) 

 Temp. setpoint wheel (rel./abs. scale) 

 Occupancy bypass button 

 Auxiliary LED 

 Service LED 

 

DIMENSIONS 

10

4

99

30

External LED

CO2 LEVEL INDICATION LED (C7110C1001A)
AUX. LED (C7110D1009A) 

OCCUPANCY BYPASS

BUTTON (C7110D1009A)

 

Fig. 1. Dimensions in mm 

Summary of Contents for C7110C1001A

Page 1: ... of outdoor air can be avoided or reduced FEATURES Fully compatible with the Excel 5000 controllers CO2 sensor employing state of the art Non Dispersion Infrared NDIR technology Selectable CO2 measurement range of 400 2000 3000 ppm Self calibrating automatic drift correction ABC algorithm based on long term evaluation External LED C7110C1001A CO2 level indication C7110D1009A auxiliary Internal Ser...

Page 2: ...nsing C7110C1001A only Range 0 50 C Output terminals 1 4 0 10 VDC for max 2 mA Accuracy sensor element See Table 1 Passive Temp Sensing C7110D1009A only Sensor terminals 1 4 Thermistor NTC20kΩ at 25 C Accuracy sensor element See Table 1 Occupancy Feature C7110D1009A only Setpoint wheel Rel 5 5 K abs 12 30 C 1 5 10 5 kΩ Occupancy bypass Pushbutton N O to COM voltage range 3 24 V internal resistance...

Page 3: ...COM COM TEMPERATURE INPUT CO2 INPUT 0 10 V NTC 20kOhm SETPOINT SETPOINT LED INPUT LED OUTPUT OCC OUTPUT OCC INPUT 24 VAC 24 VAC CO2 OUTPUT 0 10 V 24 VAC DC LINE VOLTAGE LINE VOLTAGE Fig 5 Wiring C7110D1009A to controller and separate safety transformer CONFIGURATION The wall module can be configured using its configuration jumper and or its configuration potentiometer Configuration Jumper The wall...

Page 4: ... Fig 8 Fast Background Calibration will be carried out The current level is then set to 400 ppm normal expected actual fresh air level in a single step NOTE Before starting Fast Background Calibration ventilate the room with fresh outdoor air Behavior of Service LED during Quick Calibration During Zero Calibration or Fast Background Calibration the Service LED will indicate that the given calibrat...

Page 5: ...indicates that ABC has finished switching ON NOTE Only after ABC has finished switching ON or OFF should you again remove power return the jumper to the desired range setting i e 2000 or 3000 and finally restore power The given ABC setting ON or OFF will then remain in effect even if power is subsequently removed or restored DEBUG Fig 11 Do not set jumper set to DEBUG DO NOT USE Configuration Pote...

Page 6: ...below 400 ppm the output signal will gradually rise to 2 V The Relay Output Mode In the Relay Output mode digital the Service LED see Fig 12 will either flash or be lit continuously thus indicating the actual Threshold Level setting Further the CO2 level indication LED of the C7110C1001A is lit GREEN when the CO2 level is below the threshold and YELLOW when above the threshold 10 V 500 ppm 1000 pp...

Page 7: ...tance ohms Fig 15 Temperature vs resistance for 20 kΩ sensor Temperature Setpoint Adjustment C7110D1009A Depending on the type of wheel in use on the C7110D1009A the corresponding controller must be set for either the relative or the absolute scale The relation between setpoint and resistance is given in Table 2 The accuracy of resistance is 5 in middle position e g 5225 Ω to 5775 Ω 10 in end posi...

Page 8: ...r dependent S O Calibration successful D Lit con tinuously Controller dependent S O Calibration failed C Dark Green S O CO2 1000 ppm C Dark Yellow S O CO2 1000 ppm C D Flashing Green controller dependent R O CO2 threshold C D Lit con tinuously Yellow controller dependent R O CO2 threshold C D Flashing green S O R O ABC ON C D Flashing yellow S O R O ABC OFF Example LED Behaviors Auxiliary LED Indi...

Page 9: ...RIES order no description T7460LIMITER Limiter for the temperature setpoint wheel T7460LONJACK LONWORKS or BACnet access module 5 pc set T7460 LONJACK The T7460 LONJACK ordered separately is a small board with a 3 5 mm jack When mounted to the Printed Circuit Board see Fig 17 it provides easy access to LONWORKS BACnet the wall module must be already connected to the LONWORKS BACnet network via a b...