C6097 · Edition 01.19
23
Technical data
6 .4 .2 UL, FM certified pressure switches
Type
Adjusting range
*
"WC (mbar)
Mean switching
differential at min.
and max. setting
"WC (mbar)
Max. inlet pressure
Lo
ck-
of
f
Difference
between
switching
pressure and
possible reset
"WC (mbar)
Medium
NP
T
con
ne
ct
ion
Switching
properties at
setpoint value
with
without
venting line
psi (mbar) psi (mbar)
C6097A3004
0.4 – 4 (1 – 10)
0.1 – 0.16 (0.25 – 0.4) 8.5 (600)
7 (480)
No
–
Air/gas
1/4
"
NO-to-COM
connection is
interrupted if the
pressure drops
C6097A3012
1 – 20 (2.5 – 50)
–
8.5 (600)
7 (480)
Yes
0.4 – 0.8 (1 – 2)
Air/gas
1/4
"
C6097A3038
12 – 60 (30 – 150)
–
8.5 (600)
7 (480)
Yes
0.8 – 4.8 (2 – 12)
Air/gas
1/4
"
C6097A3053
1 – 20 (2.5 – 50)
0.3 – 0.6 (0.75 – 1.5)
8.5 (600)
7 (480)
No
–
Air/gas
1/4
"
C6097A3079
12 – 60 (30 – 150)
1.2 – 2 (3 – 5)
8.5 (600)
7 (480)
No
–
Air/gas
1/4
"
C6097A3095
0.4 – 4 (1 – 10)
–
8.5 (600)
7 (480)
Yes
0.16 – 0.4
(0.4 – 1)
Air/gas
1/4
"
C6097A3111 40 – 200 (100 – 500)
–
8.5 (600)
7 (480)
Yes
2 – 7.2 (5 – 18)
Air/gas
1/4
"
C6097A3137 40 – 200 (100 – 500)
3.2 – 6.8 (8 – 17)
8.5 (600)
7 (480)
No
–
Air/gas
1/4
"
C6097B3002
12 – 60 (30 – 150)
–
8.5 (600)
7 (480)
Yes
0.8 – 4.8 (2 – 12)
Air/gas
1/4
"
NC-to-COM
connection is
interrupted if the
pressure rises
C6097B3028
1 – 20 (2.5 – 50)
–
8.5 (600)
Yes
0.4 – 0.8 (1 – 2)
Air/gas
1/4
"
C6097B3051 40 – 200 (100 – 500)
–
8.5 (600)
Yes
2 – 7.2 (5 – 18)
Air/gas
1/4
"
C6097B3085
12 – 60 (30 – 150)
1.2 – 2 (3 – 5)
No
–
Air/gas
1/4
"
C6097B3101 40 – 200 (100 – 500)
3.2 – 6.8 (8 – 17)
No
–
Air/gas
1/4
"
C6097B3119
1 – 20 (2.5 – 50)
0.3 – 0.6 (0.75 – 1.5)
No
–
Air/gas
1/4
"
* Adjusting tolerance = ± 15% of the scale value.
For further information, see page 4 (Use).