GENERAL INFORMATION 

The Honeywell Battery Sense Module is a control panel 

accessory that is used to monitor and report the backup 
battery status.  Its features are: 

 

Monitors and reports for one or two batteries.

 

 

Detects and reports low battery conditions.

 

 

Detects and reports if a battery is removed.

 

 

Provides deep discharge battery protection if AC 
power is lost and the backup battery voltage falls 

below a safety threshold of 9.5 to 10 volts.

 

Additional modules can be used for those control panels 
that use additional batteries.  

PACKAGE CONTENTS 

The following items are included: 

 

Battery Sense Module with bracket  

 

Battery Harness (qty 2)  

 

Summary of Connections label  

SPECIFICATIONS

 

Physical:  

3-1/8” L x 2-3/4” W x 3/4” H 

 

   (80mm x 70mm x 20mm)

 

Electrical: 

Input Voltage:  12VDC nominal (from control panel) 

Input Current:  20mA (max used by BSM)  
Current Handling Capability:  2.3A maximum 

(Control panel load must not exceed 2.3A.) 

 

INSTALLATION

 

1.

 

Select a suitable area in the control panel where 
the mounting will not interfere with testing or 
servicing of other components. 

2.

 

Clip the Battery Sense Module to the cabinet edge. 

 

CONNECTIONS

  

1.

 

Refer to the Connections Diagram on other side.  
When connecting leads, support the module to 

prevent stress on the circuit board.  

2.

 

Connect the module's power leads to the control 
panel's 12VDC backup battery power terminals. 

3.

 

Connect backup battery A to the module.  Then 

connect backup battery B (if present) to the module. 

4.

 

If only one backup battery is being used, depress 

the ENROLLMENT switch to toggle the Battery 

Sense Module to sense only one battery. 

ULC

 

When used with one battery and the total 
load is greater than 1.5A, jumper the 

Battery A terminals and the Battery B 

terminals on the Battery Sense Module to 
the backup battery.  

5.

 

For non-Honeywell control panels, connect the 

ZONE OUT to an unused control panel zone.  

(Do 

not use a fire zone.)

 

Note:

 For Honeywell control panels, DO NOT 

connect a zone to the ZONE OUT terminal on 
the BSM.  The Honeywell control panel will 

automatically detect a low or missing battery 
through the panel's battery cable. 

6.

 

Affix the supplied

 Summary of Connections

 label to 

the inside of the control panel.  

CONFIGURATION

 

1.

 

Refer to the control panel's installation guide for 
details on fault monitoring. 

2.

 

For non-Honeywell control panels, program the 
connected zone for the Battery Sense Module to 

detect an active high fault condition. 