–   For installation and operation, note the applicable 

national regulations and the directives of the gas 
supply company. For Germany, the valid DVGW 
Code of Practice G600 (DVGW-TRGI) applies.

–   Work on meters and the installation of meters 

which are marked with 

 and are installed in 

potentially explosive atmospheres may only be 
carried out by persons with appropriate qualifi-
cations.

–   The gas meter marked with 

 must be in-

cluded in the equipotential bond when being 
installed in a potentially explosive atmosphere, 
e.g. by connecting it to a grounded pipeline. 
Installation must be carried out in accordance 
with EN 60079-14.

–   The gas meter marked with 

 must be pro-

tected from falling parts.

–   Avoid subjecting the unit to mechanical stress 

and prevent damage. Gas meters must be in-
stalled without any mechanical stress, preferably 
only by suspending them on the connectors. 
When using additional clamps, it must be en-
sured that no lateral forces act on the gas meter. 

These can be avoided by using flexible or supple 

connection lines, for instance.

 

  If the calibration seal has been damaged or re-

moved, the gas meter is no longer approved for 
measurements which are subject to statutory 
testing. 

 

If the gas meter is stored or installed outdoors, 
protect the site against rain. Condensing humid-
ity is permitted.

 

Meters which are marked with H3 are suitable 
for installation outdoors without additional pro-
tection.

    

Remove protective caps.

 

Installation in the vertical position: connectors 
must be pointing upwards.

 

Note direction of flow (arrow).

 

The gas meter must not be in contact with ma-

sonry or other parts.

 

Ensure that there is sufficient installation space.

 

Ensure unobstructed view of the index.

 

The seal faces on the screw unions must be 

clean and damage-free.

 

Ensure that the seal is correctly seated.

Co-axial meters: 

 

The seal must be centred over the internal dia-

meter.

 

When using an elastomer seal, always use a 

pressure ring (shape A).

 

Note the installation position of the pressure ring. 

The inner beaded edge must point upwards.

 

Replace damaged pressure rings when replac-
ing the meter.

Co-axial and two-pipe meters:

 

For the compression of seals and the resulting 
tightening torques for the screw unions, the seal 
manufacturers’ specifications must be observed.

 

 Tightening torques for the recommended flat 

seals in conjunction with screw connectors 
pursuant to DIN  3376-1 and  3376-2, see 
www.docuthek.com 

 Elster-Instromet 

 Prod-

ucts 

 Gas measuring devices 

 Diaphragm 

meters 

 Ergänzung für Betriebsanleitung BK, 

Verschraubungen und Anzugsmomente für BK-
G1,6 bis BK-G25 (Supplement to BK operating
 

instructions, Screw unions and tightening tor-
ques for BK-G1.6 to BK-G25) (D).

    

Install the gas meter free of mechanical stress.

 

If a pulse transmitter IN-Z6x is used for pulse 
tapping on the gas meter marked with 

 – see 

Data sheet for pulse transmitter IN-Z6x (D, GB) 

 

www.docuthek.com 

 Elster-Instromet 

 Prod-

ucts 

 Gas measuring devices 

 Diaphragm 

meters 

 Pulse transmitter IN-Z61 and the 

standard EN 60079-14 (Explosive atmospheres).

Temperature test point

 

Temperature sensors can be inserted into the 

thermowells for measuring the gas temperature 
in the meter housing.

1

2

  

 Secure each of the temperature sensors using 

the capstan screw provided.

Pressure test point on housing 
(optional)

Summary of Contents for BK-G1.6A

Page 1: ...ified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 07 17 The following chapters have been changed Checking the usage Commissioning Accessories Technical data Declarations of conformity ATEX legend Logistics Contents Operating instructions D GB GB 1 1...

Page 2: ...C A E B Mechanical index Chekker mechanical index Absolute ENCODER index Electronic index Indication of volume at base conditions T Te TB TeB Temperature conversion mechanical electronic mechanical electronic temperature conversion and pressure correction electronic temperature conversion and pressure correction Part designations 1 3 5 7 6 2 4 1 Diaphragm gas meter BK 2 Index with index plate 3 Co...

Page 3: ...the index variant can be found at the bottom of the type label or on the index cover next to the serial number S N EI6 tm tg tb M 0102 15 ATEX 1550 X Further information can be found in the supplemen tary operating instructions of the relevant index Diaphragm gas meters with integrated valve DE 07 MI002 PTB001 S N 002545632734 class 1 5 NG 47001BM0443 DIN EN 1359 2007 BK G VALVE Vx M 0102 m3 Valve...

Page 4: ...serve the following to ensure that neither persons nor the gas meter are damaged during installation and operation Note the max allowable operating pres sure pmax and measuring range Qmax see page 2 Type label Index plate Note the permitted ambient temperature tm and gas temperature tg see page 2 Type label Index plate or page 9 Technical data The gas meters are certified for mechanical environmen...

Page 5: ...w arrow The gas meter must not be in contact with ma sonry or other parts Ensure that there is sufficient installation space Ensure unobstructed view of the index The seal faces on the screw unions must be clean and damage free Ensure that the seal is correctly seated Co axial meters The seal must be centred over the internal dia meter When using an elastomer seal always use a pressure ring shape ...

Page 6: ...e installation and tightness test are com plete see page 6 Tightness test protect the pressure test point against external access with the sealing sleeve and the seal Pressure test point on outlet connector optional BS4161 compliant pressure test nipple Use a 10 mm spanner to release tighten the test point screw The test nipple is secured to prevent it turning with the screw Opening the test nippl...

Page 7: ...lectrical circuits of pulse transmitters IN Z61 and IN Z64 are consid ered to be grounded at voltages 10 V if the plug connector housings are connected to the ground potential The intrinsically safe electrical circuits of pulse transmitters IN Z61 IN Z62 and IN Z65 are to be considered as non grounded BK G A with Absolute ENCODER index AE1 Z6 Interface description for gas meters with ENCODER index...

Page 8: ...g force and fully releases the gas supply If consumers of the customer are open pressure equalization cannot occur and the valve remains in the Released position and continues to release only the minimum gas flow rate of the bypass Closed The valve and the bypass are closed in the event of remote shut down All valve positions are kept when de energized Maintenance Removal Gas meters BK G1 6 to 25 ...

Page 9: ...e required error limits If no gas temperature tg is specified on the index plate the following applies tg tm The specified centre temperature tsp of the BK G E series and BK G B meters is not stated on the index plate but can be called up in the display using the menu Diaphragm gas meters BK with pressure test point Pressure test point 24 olive fitting to EN ISO 8434 1 L6 x M12 x 1 5 St Diaphragm ...

Page 10: ... F NL I SK RUS E RO SRB Declarations of conformity Scans of all valid Declarations of conformity see www docuthek com Elster Instromet Diaphragm gas meters BK G M BK G C BK G MT BK G CT without ATEX declaration ...

Page 11: ...GB 11 D GB Diaphragm gas meters BK G M BK G C BK G MT BK G CT with ATEX declaration ...

Page 12: ...GB 12 GB F NL I SK RUS E RO SRB Diaphragm gas meters BK G M BK G C BK G MT BK G CT with RFID passive tag and ATEX declaration ...

Page 13: ...GB 13 D GB Diaphragm gas meters BK G A BK G AT ...

Page 14: ... for Zone 2 c Constructional safety explosion protec tion type IIB IIA Explosion group for gases TX No intrinsic heating T1 Temperature class maximum allowable surface temperature 450 C T4 Temperature class maximum allowable surface temperature 135 C T6 Temperature class maximum allowable surface temperature 85 C Gc Equipment protection level for Zone 2 Ta Ambient temperature Logistics Transport D...

Reviews: