GB-4
D
GB
F
NL
I
SK
RUS
E
RO
SRB
BK-G..E, BK-G..ET, BK-G..ETB with index EI
Category devices:
BK
Elster GmbH, Strotheweg 1
D-49504 Lotte, Germany
0044 II 3/1G IIB T4
TÜV 14 ATEX 143120 X
t
amb
= t
gas
= –20 °C ... +55 °C
Use as follows:
Category, internal: 3 (Zone 2), external: 1 (Zone 0).
Type of atmosphere: gases, hazes and vapours.
For the ambient and gas temperatures of the ATEX
Zones, see illustration.
Category devices:
BK
Elster GmbH, Strotheweg 1
D-49504 Lotte, Germany
13 ATEX 1389 X
II -/3 G IIA T1
Use as follows:
Category, internal: none, external: 3 (Zone 2).
Type of atmosphere: gases, hazes and vapours.
BK-G..B
BK
Elster GmbH, Strotheweg 1
D-49504 Lotte, Germany
TÜV 12 ATEX 098560 X
II -/2 G IIA T4
Use as follows:
Category, internal: none, external: 2 (Zone 1).
Type of atmosphere: gases, hazes and vapours.
BK-G..E with EI5
M ...
Elster GmbH, Strotheweg 1
49504 Lotte, GERMANY
S/N
: ............
EI5.0x
0102
16ATEX1551X
tamb = tgas = –20 °C ... +55 °C
II 3Gic c IIA T1Gc
Use as follows:
Category: 3 (Zone 2).
Type of atmosphere: gases, hazes and vapours.
BK-G..ETe with EI6
EI6.0x
t b
t m
t g
IP
Valve Ve
18ATEX1678 X
tamb = tgas = –25 °C ... +55 °C
M ...
0102
GPRS
II -/3 G ic c IIB T4 Gc
Use as follows:
Category, internal: none, external: 3 (Zone 2).
Type of atmosphere: gases, hazes and vapours.
Installation
WARNING
Please observe the following to ensure that neither
persons nor the gas meter are damaged during
installation and operation:
– Note the max. allowable operating pres-
sure p
max
and measuring range Q
max
, see
page 2 (Type label/Index plate).
– Note the permitted ambient temperature t
m
and
gas temperature t
g
, see page 2 (Type label/
Index plate) or page 9 (Technical data).
– The gas meters are certified for mechanical
environments pursuant to Class M1 of Directive
2004/22/EC. When installed, the meters must
not be subject to permanent vibration such as
that caused by machines in the vicinity. In case
of doubt, vibration isolation must be provided.
For gas meter versions BK..A, BK..E and BK..B,
Class E2 for electromagnetic environments also
applies.
– The dangers of chemical reactions between
gas meter parts and the chemical substances
in the environment are to be discussed by the
manufacturer and the operator and must be
eliminated.
– When installing the diaphragm gas meter BK with
integrated valve, make sure that no dirt particles
get into the meter and thus into the valve.
– The yellow sealing sleeve protects the pressure
test point on the gas meter. It may only be opened
for connecting a pressure measuring line.
– Use seals made from tested materials. Elastomer
seals or asbestos-free flat seals from Elster are
recommended.
– Only use the seals once.
– For meters resistant to high temperatures, only
use seals tested to be resistant to high tempera-
tures.