
BCU 460, BCU 465 · Edition 11.19
98
Parameters
11 .8 .12 Combustion mode
Parameter A074
The type of combustion in which the ignition takes
place can be set using parameter A074.
Parameter A074 = 0: Flame mode. The burner is al-
ways started with ignition in Flame mode and in High
temperature mode. Flame control is provided in High
temperature mode by the high temperature monitoring
system.
Parameter A074 = 1: Flameless/menox®. Only with
BCU..D2.
FCU
Process Control (PCC)
PZL
DG
BCU 465..F1
µC
V1
V2
61
60
6
7
65
36
HT
FLO
VR..N
PLC
STM
The High temperature and Flameless mode inputs
(terminals 6 and 7) must receive a signal to switch to
Flameless mode. The timing of the switchover is con-
trolled by the parameter “Flameless operation” (A064).
I
n Flame mode (< 850°C), the burner is started con-
ventionally (as with A078 = 0) with the pre-ventilation
time t
VL
defined in parameter A036. The air control
valve is in the “high” position for Flame mode.
03
02
04
2
1
51
61
60
6
1
7
36
t
t
FS1
t
SA1
t
VL
65
PZL
HT
ϑ
42
FLO
The switchover from Flame mode to Flameless mode
is performed either immediately or the next time the
burner is started depending on the setting made in
parameter A064. To switch to Flameless mode, the
HT signal from the STM (terminal 6) and the signal for
Flameless mode (FLO) must be supplied to the BCU by
a separate control unit (terminal 7).
▼