In the “draw-through” unit ventilator (Fig. 21) the fan draws
filtered outdoor and return air across the coil and blows the
conditioned air into the space.
Face and bypass dampers are frequently found on unit
ventilators wherein the room controller modulates the dampers,
and the coil valve closes after the face damper is closed.
CONTROL
Unit ventilator control regulates the amount of outdoor air
introduced into a space and the amount of heating or cooling
medium required to heat or cool the room. Day/night systems
can lower the setpoint and cycle the fan during unoccupied
hours to maintain minimum temperatures and save energy.
ASHRAE Control Cycles
ASHRAE classifies the control of unit ventilators as follows:
— Standby/Warm-up Stage (can be used with any of the
following cycles)
— Cycle I–Fixed Maximum Percentage of Outdoor Air
— Cycle II–Fixed Minimum Percentage of Outdoor Air
— Cycle III–Variable Outdoor Air
These classes, defined around the 1950’s, simplified the
specifications for unit ventilators, unit ventilator controls and
sequences, and the factory mounting of control components.
These cycle definitions are for heating only, although ASHRAE
recognized that cooling coils may also be required. Cycles I,
II, and III differ in the sequence of damper action in response
to a rise in space temperature and in the amount of outdoor air
admitted at various temperatures. ASHRAE control cycles may
be implemented by pneumatic, electric, electronic, or digital
control.
STANDBY/WARM-UP STAGE
During cold room periods, all three cycles position the valves
and dampers the same. Figure 23 shows the standby/warm-up
stage in which the unit ventilator fan is shut down (manually or
by time clock). The outdoor air damper is closed, and the return
air damper is full open. The heating coil valve is open. The coil
acts as a convector as air circulates by convection across the
coil. The room thermostat modulates the valve, closing the valve
as space temperature rises above setpoint. The fan does not
operate in the standby stage. During the warm-up stage, the
fan energizes and the unit recirculates space air for a rapid rise
in space temperature. The thermostat signal operates the valve
to control the heat.
Fig. 21. Draw-Through Unit Ventilator.
Some unit ventilators use separate heating and cooling coils
or a combination hot-water/chilled-water coil. Figure 22 shows
a typical air conditioning unit ventilator with two separate coils.
The heating medium may be hot water, steam, or electric
resistance elements, and the cooling medium may be chilled
water or DX refrigerant. If heating and cooling sources are both
water, they are sometimes combined in a single coil by providing
separate sections of the coil for each function. With DX cooling,
the condensing unit may be an integral part of the unit ventilator
or may be remotely located.
C3036
DISCHARGE
AIR
WALL
OUTDOOR
AIR
MIXING
DAMPER
RETURN
AIR
FACE AND
BYPASS
DAMPER
FILTER
HEATING
COIL
FAN
Fig. 22. Unit Ventilator with Separate
Heating and Cooling Coils.
C3035
DISCHARGE
AIR
WALL
OUTDOOR
AIR
MIXING
DAMPERS
RETURN
AIR
COOLING
COIL
DRAIN PAN
FILTER
HEATING
COIL
FAN
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...