ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
366
With both valves operating, as the total demand drops below
the capacity of the large valve for five minutes, the small valve
shall close. With the large valve operating, as the demand drops
below the capacity of the small valve for five minutes, the large
valve shall close and the small valve shall assume the load.
Demand Limiting:
A large valve Cv limiting parameter shall be provided and
set such that upon full demand, the valve Cv shall not exceed
the design Cv of 51.
All valve timings and parameters shall be field adjustable by
the owner.
THREE-WAY VALVE
The supply water temperature to the radiators (Fig. 96) is
reset by the controller modulating the three-way valve. The
controller modulates the three-way valve to maintain the reset
schedule in response to temperature changes at the outdoor air
sensor and the supply water sensor. Pump runs continuously
during the heating season. As water temperature changes, the
heat output changes linearly. This allows accurate changes in
heating plant capacity as a function of outdoor air temperature
or some other signal to match the load.
Hot Water Control Method Selection
Supply water temperature control is suitable for controlling
the heat delivery from a heat exchanger or a secondary water
pump.
Flow control is acceptable for controlling individual terminal
units such as convectors, fan coils, or induction units. An equal
percentage characteristic valve complements the water to air
heat exchanger characteristic of heat output versus flow. The
result is a relatively linear heat output as a function of stem
position (Fig. 97). The heat output is relatively constant,
providing optimized controllability of heat exchangers such as
converters, fan coils, and induction units.
Fig. 96. Radiators with Scheduled Water
Temperature Using Three-Way Valve.
Coordinating Valve Selection and System Design
A prerequisite to good modulating control of water systems
is a coordinated design of the entire water system. All control
valves must be sized so that the system will deliver design flow
at full load and not generate uncontrollable conditions at
minimum load.
Control valve selection is based on pressure differentials at
the valve location, full load flow conditions, valve close-off,
and valve controllability at minimum load conditions.
Generally, for smooth modulating control, the no-flow
pressure differential should not exceed the full flow differential
by more than 50 percent.
C2917
3-WAY
VALVE
MINIMUM
BOILER
FLOW (BYPASS)
BOILER
TO OTHER
RADIATORS
SUPPLY WATER
SENSOR
CONTROLLER
OUTDOOR
AIR
SENSOR
Fig. 97. Control of a Water Heat Exchanger Using an
Equal Percentage Characteristic Valve.
CHILLED WATER DISTRIBUTION SYSTEMS
GENERAL
Chilled water systems for cooling of commercial buildings
usually provide water between 40 and 50F to finned coils in
room units or air handlers.
The amount of water delivered to the cooling coils and/or
produced by chillers is related to temperature difference (TDW)
across the coil or chiller and energy (tons of refrigeration) by
the equation:
C2918
HEA
T
EXCHANGER
OUTPUT
VALVE POSITION
WA
TER FLO
W
CL
OP
VALVE POSITION
CL
OP
gpm =
Tons x 24
TDW
Where:
1 Ton = 12000 Btuh
24 = a constant
TDW = water temperature difference in degrees F
EXAMPLE:
Given: A 100 ton chiller with a TDW of 10F.
gpm =
100 Tons x 24
10
= 240 gpm
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...