![Honeywell AUTOMATIC CONTROL Engineering Manual Download Page 337](http://html.mh-extra.com/html/honeywell/automatic-control/automatic-control_engineering-manual_149859337.webp)
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
327
Fig. 36. Graphic for Tower Free Cooling System with Dual Chillers.
TOWER FREE COOLING, DUAL CHILLERS
FUNCTIONAL DESCRIPTION
Item No.
Function
1,2
Chilled water pumps produce flow through
chillers or plate/frame heat exchangers.
3,4
Free cooling mode initiated when OA WB
drops to setpoint.
5
Tower water entering temperature, operator
information.
6,7
Setpoints indicate need for cooling tower and
chilled water.
8
Minimum condenser water temperature setpoint
provides free cooling low limit.
9
In free cooling mode, tower will produce water
about 7F above OA wet-bulb temperature, and
HX will cool chilled water to within 2 to 3F of
condenser water temperature, so the sum of
these dictates when to activate free cooling.
10-13
Maintains condenser water temperature entering
chiller during period when tower is pulling
water temperature down to free cooling setpoint
value and the temperature is too low for chiller.
14-17
Valves direct water from chiller/condenser to
HX when condenser water reaches setpoint.
18,19
Chiller Status.
20
Operator information.
21
Prevents tower from cooling water below
minimum value that chiller can tolerate (during
chiller cooling mode).
22,23
Tower fans modulate to maintain condenser
water setpoint.
24
CHILLER-AUTO-TOWER software mode
selection function.
25
Prevents chilled water temperature setpoint
from dropping below the design minimum.
26-45
Operator information (see chiller control and
cooling tower control examples).
46
Icon, to display cooling tower control data.
47
Icon, to display chiller control data.
21
100
68
72
76
66
66
72
66.0
49
55
42.0
50.2
60.0
10.0
45
51
60
60
76
60
60
76
1
-
+
-
+
78
00
ON
OFF
OFF
OPEN
OPEN
OUTSIDE
AIR
WET BULB
WET BULB
DRY BULB
CHILLER/ FREE
COOLING SETPOINT
CHILLER/ FREE
COOLING
CURRENT MODE
FREE COOLING OA WB SETPOINT = CHILLED WATER
TEMPERATURE SETPOINT MINUS DEGREES
CHILLER/ FREE
COOLING
CURRENT MODE
MINIMUM
SETPOINT
CHILLER
MINIMUM
SETPOINT
FREE COOLING
MINIMUM
SETPOINT
CONDENSER WATER SETPOINTS
CURRENT
SETPOINT
OPEN TO
CHILLER
CHILLER 1
CHILLER 2
CURRENT
SETPOINT
PHX 2
P2
P1
LOAD
STATUS
56
56
0
26
26
100
0
41
CHILLER
51
ON
ON
P4
41
22
23
42
40
5
6
44
43
38
3
8
4
9
26
24
TOWER
CONTROL
46
CHILLER
CONTROL
47
25
7
20
15
1
30
31
32
10
45
39
18
19
11
34
37
13
35
16
12
29
28
2
17
36
ON
00
OPEN TO
CHILLER
00
27
PHX 1
1 = CHILLER
2 = AUTO
3 = TOWER
33
14
P3
M15049
COOLING
TOWER 1
COOLING
TOWER 2
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...