![Honeywell AUTOMATIC CONTROL Engineering Manual Download Page 32](http://html.mh-extra.com/html/honeywell/automatic-control/automatic-control_engineering-manual_149859032.webp)
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CONTROL FUNDAMENTALS
22
Fig. 33. Relationship of Offset to Load
(Heating Application).
The throttling range is the amount of change in the controlled
variable required for the controller to move the controlled
device through its full operating range. The amount of change
is expressed in degrees Fahrenheit for temperature, in
percentages for relative humidity, and in pounds per square
inch or inches of water for pressure. For some controllers,
throttling range is referred to as “proportional band”.
Proportional band is throttling range expressed as a percentage
of the controller sensor span:
“Gain” is a term often used in industrial control systems for
the change in the controlled variable. Gain is the reciprocal of
proportional band:
The output of the controller is proportional to the deviation
of the control point from setpoint. A proportional controller
can be mathematically described by:
V = KE + M
An example of offset would be the proportional control of a
chilled water coil used to cool a space. When the cooling load
is 50 percent, the controller is in the middle of its throttling
range, the properly sized coil valve is half-open, and there is
no offset. As the outdoor temperature increases, the room
temperature rises and more cooling is required to maintain the
space temperature. The coil valve must open wider to deliver
the required cooling and remain in that position as long as the
increased requirement exists. Because the position of the final
control element is proportional to the amount of deviation, the
temperature must deviate from the setpoint and sustain that
deviation to open the coil valve as far as required.
Figure 33 shows that when proportional control is used in a
heating application, as the load condition increases from 50
percent, offset increases toward cooler. As the load condition
decreases, offset increases toward warmer. The opposite occurs
in a cooling application.
Outdoor Air
Discharge Air
Temperature
Temperature
Condition
(F)
(F)
Outdoor design
temperature
0
100
Light load
70
70
100
70
0
(FULL
RESET)
70
(RESET
START)
OUTDOOR AIR TEMPERATURE (
°
F)
DISCHARGE AIR
TEMPERATURE SETPOINT (
°
F)
C2719
(FULL RESET)
Where:
V = output signal
K = proportionality constant (gain)
E = deviation (control point - setpoint)
M = value of the output when the deviation is
zero (Usually the output value at 50 percent
or the middle of the output range. The
generated control signal correction is added
to or subtracted from this value. Also called
“bias” or “manual reset”.)
Although the control point in a proportional control system
is rarely at setpoint, the offset may be acceptable.
Compensation, which is the resetting of the setpoint to
compensate for varying load conditions, may also reduce the
effect of proportional offset for more accurate control. An
example of compensation is resetting boiler water temperature
based on outdoor air temperature. Compensation is also called
“reset control” or “cascade control”.
COMPENSATION CONTROL
GENERAL
Compensation is a control technique available in proportional
control in which a secondary, or compensation, sensor resets
the setpoint of the primary sensor. An example of compensation
would be the outdoor temperature resetting the discharge
temperature of a fan system so that the discharge temperature
increases as the outdoor temperature decreases. The sample
reset schedule in Table 2 is shown graphically in Figure 34.
Figure 35 shows a control diagram for the sample reset system.
Table 2. Sample Reset Schedule.
Fig. 34. Typical Reset Schedule for Discharge Air
OFFSET
OFFSET
50%
LOAD
COOLER
WARMER
SETPOINT
0%
LOAD
CONTROL POINT
C2096
100%
LOAD
Proportional Band =
Throttling Range
Sensor Span
x 100
Gain =
100
Proportional Band
Control.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...