background image

N

L

AgoraLED IP42

GB

AgoraLED

Test

Test

LAMP FAULT

BATT FAULT

POWER

CHARGE

EMERGENCY

LIGHTING

AGORALED

302mm

94mm

330mm

210mm

234mm

AgoraLED IP42

AgoraLED IP65

Test

Test

LAMP FAULT

BATT FAULT

POWER

CHARGE

EMERGENCY

LIGHTING

AGORALED

307mm

100mm

333mm

210mm

234mm

Dimensional Drawings:

Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway 

 http://www.hls-nordic.com 

Installation:

(Wall Mounting Only)

2

Cover
retaining
screws

Mounting Holes

Test

Test

LAMP FAULT

BATT FAULT

POWER

CHARGE

EMERGENCY

LIGHTING

AGORALED

3

4

5

Step 1:

 Hold the device on the wall and mark the holes with a marker. The distance between the mounting holes is 

234mm. Drill the holes. Use the supplied mounting accessories to mount the device. Remove the four cover 
retaining screws.

Step 2:

 Install the cable grommet and pass the round cable. Connect the cables to the respective positions in the 

terminal block L for phase and N for neutral. 

Always use in any case round mains cable, with external diameter 

of 6-9mm (H05RN-F type 2x1mm or any other type, at least equal to it’s mechanical and electrical 
properties). ATTENTION!! The cable must not be deformed In any way.

Step 3:

 Install the battery cable connectors to the batteries taking care of the polarity, black cable (-) and red cable (+).

Step 4:

 In case you use a module connect it on the PCB.

Step 5:

 The user can select one of the 3 available minimum durations: 1 hour, 3 hours and 8 hours. The selection must 

be done while the luminaire is disconnected from AC and battery supplies. The selection is achieved through 
Switches 2 & 3 of DS1. Switch 1 and 4 are not used. Two additional labels are included in the package, one for 3 
hours duration (180) and one for 8 hours duration (480). Depending on the selected duration, the installer must 
replace the default 1 hour (60) label with one that has the required duration. 

Please take notice of the 

orientation of the label.

Step 6:

 There is a terminal block for connection to the (optional) communication modules (elBus, DALI and pot. free), in 

the lower left corner of the PCB. The terminals are marked C1 and C2.

Step 7

: Make a hole in the right side of the luminaire, install the rubber gasket and make a hole in the center by using a 

small screwdriver. Pass the round cables through the gasket and connect it on the terminals.

Step 8:

 Close the front cover and fasten it with the removed screws. (Tightening torque 1 N*m)

6

C1C2

AgoraLED IP65

N

L

2

6

7

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

1h

(default position)

3h

8h

Dip Switch Positions