N8583V3  7/05  Rev. A 

 

ADEMCO 5809 

Rate-Of-Rise Heat Detector 

INSTALLATION AND SETUP GUIDE 

GENERAL INFORMATION 

The ADEMCO 5809 Rate-of-Rise Heat Detector is a wireless 
device used with ADEMCO alarm systems that support 5800 
series devices.   

The 5809 combine both rate-of-rise and fixed temperature 
sensors.  The 5809’s rate-of-rise thermostat senses the rise in 
temperature and signals an alarm if the rise is 15

°

F (8

°

C) or 

more per minute.  Fires typically cause a rapid rise in 
temperature in the surrounding area.  A built-in fixed 
temperature sensor will also signal an alarm if the ambient 
temperature rises above 135

°

F (57

°

C).   

WARNING:

  The 5809’s fixed temperature sensor will be 

permanently damaged if the 5809 is installed, stored or shipped 
in environments where temperature exceeds 120

°

F.   

NOTES:   

• 

If the fixed temperature sensor activates, the 5809 
must be replaced.   

• 

An installation site where the ambient temperature 
exceeds 100

°

F for extended periods is not 

recommended.   

A 3-volt lithium battery powers the 5809.  If the battery voltage 
gets too low, the 5809 send a low battery signal to the control 
panel.   

The 5809 also include a tamper switch, which causes a trouble 
signal to be sent to the control if the unit is removed from the 
mounting base.   

A built-in activation button, located on the detector assembly, is 
used when programming the unit’s serial number at the control 
and when testing the unit.   

INSTALLING THE BATTERY 

Important Notes:   

• 

Use 3-volt lithium battery:  Duracell DL 123A or  
Panasonic/Sanyo/Varta/Tekcell CR123A.   

• 

Observe polarity.   

• 

When replacing the battery, wait at least 30 seconds 
after removing the old battery, before installing the 
new one.   

Remove the detector assembly from its mounting base and 
install a 3-volt lithium battery as shown below.   

BATTERY

5809EN-003-V0

 

PROGRAMMING THE UNIT 

The transmitter’s serial number must be enrolled in the control 
panel before usage in the system.  Refer to the Installation and 
Setup Guide for which this device is to be used for 
programming procedures for enrolling transmitter serial 
numbers.  Before programming do the following:   

1. 

Remove the detector assembly from its mounting base by 
twisting the detector assembly counter-clockwise and 
withdraw from the base.   

2. 

Install the battery (if not already installed).  Observe 
polarity!   

3. 

Enter the control’s programming mode and follow the 
control’s programming instructions.  When programming 
this transmitter at the control, note the following:   

• 

Input Type = 3 (Supervised RF) 

• 

Loop number = 1 

 

Transmit from the detector when prompted (momentarily 

 

depress the activation button shown below).  You can also 

 

manually enter the detector’s serial number.   

4. 

Test the detector after enrolling into the system.  Refer to 
the Testing section.   

5809EN-001-V0

ACTIVATION

BUTTON

DETECTOR

ASSEMBLY

INDEX

TAB

TAMPER

SWITCH

 

MOUNTING THE DETECTOR 

You can mount the 5809 on a wall or ceiling within the 
protection area:   

• 

Wall Mounting:  Mount the detector 4” - 6” from the 
ceiling.   

• 

Ceiling Mounting:  Mount the detector at least 4” from 
any wall.  Make sure the normal ceiling temperature 
will not exceed 100

°

F.   

• 

Refer to NFPA Standard 72 for detector spacing and 
other requirements.  Maximum spacing for UL 
installations is 50’x50’.   

• 

Avoid mounting the detector near heat generating 
devices (e.g. ovens, heat vents, furnaces, boilers).   

IMPORTANT:

   

Heat detectors should be used for property protection.  
Reliance should not be placed solely on heat detectors for 
life safety.  When life safety is involved, smoke detectors 
MUST also be used.  Detectors must not be painted.   

WIRELESS TRANSMISSION PATH TEST 

A good RF transmission path must be established from the 
proposed mounting location before permanently installing the 
detector.  To determine that there is good signal reception from 
the proposed location, perform the test procedure described in 
TESTING THE DETECTOR section.   

Once a good RF transmission path is confirmed, mount the 
detector as follows:   