ADEMCO 4204 Relay Module – Installation Instructions

 

 
GENERAL INFORMATION 

The ADEMCO 4204 Relay Module provides from one to four 
dry, form-C (SPDT) relay outputs to compatible 
control/communicators. It connects to the control’s keypad 
wiring terminals. 
 
The 4204 can be mounted inside the control’s cabinet or 
mounted remotely depending on the application. Refer to the UL 
notes below for certain restrictions. 
 
If mounted remotely, the 4204 has a built-in tamper switch that 
allows it to detect and report the removal of its cover to the 
control.  Second, communication to the 4204 is supervised so 
that it cannot be disconnected from the keypad wiring without 
detection by the control. If the wiring is cut, a tamper or alarm 
signal will result, to indicate that this device (and possibly other 
devices connected to the keypad wiring) has become 
inoperative. 

 

INSTALLATION 

For UL Installations

When used with controls that do not support cover tamper or 
supervise communications wiring to the 4204, mount the 4204 
inside the control’s cabinet. 
 
When used with controls that support cover tamper and 
supervise communications wiring to the 4204, mount the 4204 
may either be mounted inside the control’s cabinet or mounted 
remotely. 
 

 

 
 

 

CUL

 

NOTE: The maintenance instructions shall detail all test 
and maintenance instruction codes and software 
necessary to provide test and inspection requirements 
of CAN/ULC-S536, Standard for the Inspection and 
Testing of Fire Alarm Systems 

 
 
When mounted inside the control’s cabinet, some controls allow 
the 4204 to be mounted horizontally as follows: insert the self-
tapping screws (provided) in two adjacent raised tabs on the 
back of the cabinet.  Leave the heads projecting 1/8”.  Hang the 
4204 on the screw heads via two of the slotted holes on the 
back of its housing.  The 4204’s cover need not, in this case, be 
tamper-protected.  Set DIP switch 1 to “ON” if the cover is not 
used (see table).  See the control’s instructions for additional 
information. 

 
 
 
When the 4204 is mounted remotely, it can be mounted 
horizontally or vertically and the built-in tamper switch can be 
used.  Wires can exit from the side or via the breakout on the 
back of its housing.  The DIP switch must be set with its position 
1 “OFF” and when the installation is completed, the unit’s 
tamper-protected cover must be replaced. 
 

NOTE:

 For EN50131-3 compliance a tie-wrap must be secured 

around the case of a remotely mounted 4204.  
Apply tie-wrap around the case to the right of the large zone 
wire opening (4-inch case width). This is in opposition of the 
tamper switch and magnet. 

 
NOTE:

 CE installations require maximum cable length of 30 

meters. 
Affix the connections label that accompanies the 4204 to the 
inside of the 4204’s cover (if the cover is used) or to the inside of 
the control’s cover. 

 

 

CONNECTIONS AND SETTINGS 

 

Select and set an address for the 4204, using its DIP switch as 
shown in the DIP switch table.  Each 4204 must be assigned a 
unique address so the control can identify and communicate 
with the 4204.  The address to set is determined by the 
particular control to be used. See the control’s installation 
instructions.  As shipped, the DIP switch is set for address “0”. 

 

UL

 

 

For UL fire installations, no more than 
one wire per terminal may be 
connected. 

 

Use only 14-22AWG wire.

 

 

NOTE:

 All power-limited wiring must be separated from non-

power limited wiring by ¼”. 

 

Make connections to the 4204’s four relays via 12-position 
terminal block TB2.  Refer to the control’s installation 
instructions for specific information on how to program the 
activation options for the relays. 

 

Make connections to the control’s keypad wiring points via 4-
position terminal block TB1, the 4-pin plug, or both (wire color 
connections are the same).  See the diagram on the other side 
of this page. 

 

 

SPECIFICATIONS 

Physical:  

6-7/16” W x 4-1/4” H x 1-1/4” D 

 

(163mm x 108mm x 32mm)

 

Electrical: 

Input Voltage: 

12VDC nominal (10-14VDC, from  
control’s remote keypad connection 
points) 

Input Current:   

15mA s 40mA per active relay 

Contact Rating: 

2A max. at 28VDC/AC (resistive loads) 

 

UL

 

 

For dry, indoor use only.  Do not install in air-
handling spaces. 

 

For UL Commercial Burglary installations, the 
4204 must be tamper protected or mounted in 
a tamper-protected cabinet.   

 

In Commercial Fire applications, the module 
cannot be mounted in the control unit’s 
cabinet, but must be mounted in an external 
UL864-listed cabinet. 