FireLite SLC Wiring Manual —
P/N 51309:R3
7/29/2019
Introduction
SLC Capacity
SD365CO
- addressable device that provides both fire and carbon monoxide (CO) detection. It combines four separate sensing elements
in one unit (smoke, CO, light/flame, and heat) to sense multiple components of a fire. The detector’s electrochemical sensing cell creates
a separate signal for life safety CO detection. This model functions in LiteSpeed only.
BEAM355
- An addressable long range projected beam smoke detector designed to provide open area protection. The
BEAM355S
has
an integral sensitivity test feature that consists of a test filter attached to a servomotor inside the detector optics.
DNR(W)
- Innovair Flex, intelligent, non-relay, low flow, photoelectric duct detector housing. This requires the SD355R or SD365R
photoelectric smoke detector. Accommodates the installation of the CRF-300 relay module. The
DNRW
is a watertight housing.
OSI-RI-FL
- An addressable long range projected beam smoke detector designed to provide open area protection. Operates in LiteSpeed
or CLIP mode.
1.4.7 Manual Pull Station
The
BG-12LX
is a dual-action pull station that, when activated, provides an addressable identification and its location to the control
panel. An addressable monitor module is mounted inside the pull station to facilitate servicing and replacement.
1.4.8 Wireless Gateway
W-GATE:
The Wireless Gateway acts as a bridge between a group of wireless fire devices and a LiteSpeed SLC loop on the ES-50X,
ES-200X, or MS-9200UDLS. It is powered by the SLC loop or by a regulated, external 24VDC UL listed power supply. Available wire-
less devices include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, and a monitor
module. For details about wireless devices, system setup, and operation, see the
SWIFT™ Smart Wireless Integrated Fire Technology
Instruction Manual
.
1.4.9 300 Series Addressable Devices
Fire•Lite’s 300 Series of addressable devices are fully compatible with the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-
9600LS(C/E), MS-9600UDLS/E, MS-9050UD, ES-50X, and ES-200X FACPs. The devices must be configured for CLIP (Classic
Loop Interface Protocol) Mode operation. The address of 300 series devices cannot be set above 99. Compatible devices include:
1.4.10 900 Series Addressable Devices
Fire•Lite’s 900 Series of addressable devices are fully compatible with the MS-9200UDLS/E and MS-9050UD/E FACPs, however they
are
not for use in the United States or Canada
. The devices must be configured for CLIP (Classic Loop Interface Protocol) Mode opera-
tion. The address of 900 series devices cannot be set above 99. Compatible devices include:
Refer to the manufacturer’s installation instructions for information on wiring and programming.
1.5 SLC Capacity
The protocol selected for an SLC loop determines the maximum number of devices that can be handled by the loop. See Section 1.3,
“Polling Protocols”. Within those limits, the individual control panel may have additional restrictions. See the specific installation man-
ual for this information.
1.6 SLC Performance
SLC performance depends on the type of circuit (Class A, Class B, or Class X) and the components on the circuit.
NOTE:
The W-GATE, as part of the wireless network, has been tested for compliance with the Federal Communications Commission
(FCC) requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the
USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this
product may be legally used outside the USA.
• SD300 Photo
• M300 Monitor Module
• SD300T Photo w/Thermal
• M301 Mini Monitor Module
• CP300 Ionization
• M302 2-wire Monitor Module
• BG-10LX Pull Station
• C304 Control/Relay Module
• SD992 Photo
• MMF-900 Monitor Module
• H995 Photo w/Thermal
• MMF-902 Interface Module
• MCP900 Call Point/Pull Station
• I900 Isolator Module
• CMF-900 Control Module
• IO900 Input/Output Module
• B901 Base
• CP900 Programming Tool
NOTE:
SLC operation meeting Class X requirements isolates each device on the SLC from faults that may occur within other areas of the
SLC.