Emergency Voice System Operation
11-10
11.7.4
Emergency Page
An emergency page can occur when:
1.
Only the emergency system is active and the user has gained EVS Control.
2.
Only fire alarm is active, custom EVS is higher priority than fire alarm and the user has gained EVS Control.
•
This will trigger the EVS system and enable mapping for 'Custom EVS' and 'General
EVS'.
11.7.5
Paging
If there are no active emergency or fire system events, the microphone at an LOC can be used for paging by
following these steps:
1.
Remove the microphone from its cradle.
2.
Press the push-to-talk button on the microphone.
3.
Use the Select Keys on the LOC to toggle the output areas to page to with the microphone (illuminates the
green LEDs).
Note: The Ready to Talk LED will illuminate after an output area has been activated.
4.
Speak into the microphone.
5.
Release PTT button when finished.
READY TO TALK LED