Model 6820 / 6820-EVS Installation Manual
LS10144-001SK-E
10-17
Figure 10-9 Wiring Configuration for Solenoid
* When ordering, order as P/N 7641-L8
10.7.1
Single Interlock Zone Releasing
A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch.
Conditions Required for an Pre-Alarm Output Activation
If any single addressable detector is activated, the “Pre-Alarm” output will activate. This alerts the user that the
initial stages required for a release condition are present. (Also refer to Table 10-4.)
Conditions required for an General Alarm and Release Output Activation
If two or more addressable detectors, or a manual release switch activate, the “Alarm” and the “Release” outputs
Viking
11591
24 VDC
417
11595
24 VDC
417
11592NC
24 VDC
416
16360
24 VDC
500
Important!
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Table 10-3: Approved Releasing Solenoids
Manufacturer
Part Number
Rated Voltage,
DC
Rated Current,
Milliamp
Model 7641-L8
Must Mounted
at the Solenoid