Honeywell 4219 Installation And Setup Manual Download Page 1

 

 

 

 

 

4219 

Wired Zone Expander Module 

INSTALLATION AND SETUP GUIDE 

GENERAL INFORMATION 

This  module  adds  up  to  eight  end-of-line  resistor  supervised  zones 
to  compatible  control/communicators  via  the  control’s  keypad 
wiring.   

The  module  may  be  mounted  within  the  control’s  cabinet  (if  room 
permits), or remotely.  If mounted remotely, there are provisions to 
tamper  protect  the  unit.    Communication  to  the  module  is 
supervised so that it cannot be disconnected from the keypad wiring 
without  detection  by  the  control.    If  the  wiring  is  cut,  a  tamper 
alarm or signal will result, to indicate that this device (and possibly 
other similarly connected devices) has become inoperative.   

IMPORTANT

:  Some  carbon  monoxide  detectors  may  not  be 

compatible  with  the  Honeywell  4219  hardwire  zone  expanders. 
When using carbon monoxide detectors in systems that support the 
4219  zone  expanders,  install  the  detectors  only  on  the  basic 
hardwire  zones  of  the  system  control  panel,  and  NOT  on  the  zone 
expanders. 

INSTALLATION 

 

1. Power should be disconnected before proceeding.   

2.

 

Be sure to mount the 4219 before making any wire 
connections.

 

When  the  module  is  mounted  remotely,  holes  on  the  back  of  the 
module’s housing permit it to be mounted horizontally or vertically.  
Wires  can  exit  from  the  side  or  the  breakout  on  the  back  of  its 
housing.    For  tamper  protection,  attach  the  tamper  magnet 
(provided) (Figure 1) to the module inside cover.  Place DIP switch 
position  #8  in  the  OFF  position.  Affix  the  connections  label  that 
accompanies the module to the inside of the module’s cover.  When 
the installation is complete, put the modules cover on.  The magnet 
attached to the cover, positioned near the reed switch, will cause a 
tamper signal to be sent to the control if the cover is removed.   

When  the  module  is  to  be  mounted  inside  the  control’s  cabinet, 
mount  it  horizontally  to the  raised  tabs  at  the  back  of  the  cabinet.  
Insert self-tapping screws (provided) in two adjacent raised tabs at 
the back of the cabinet.  Leave the heads projecting 1/8”.  Hang the 
module on the screw heads via two slotted holes on the back of the 
module’s  housing.    When  the  module  is  installed  in  the  control’s 
cabinet, it need not be tamper protected.  

NOTE:

 For EN50131-3 compliance a tie-wrap must be secured 

around the case of a remotely mounted 4219.  

Apply  tie-wrap  around  the  case  to  the  right  of  the  large  zone  wire 
opening  (4-inch  case  width).  This  is  in  opposition  of  the  tamper 
switch and magnet. 

Affix  the  connections  label  that  accompanies  the  module  to  the 
inside of the control’s cover.   
See  the  control’s  installation  and  setup  guide  for  additional 
information.   

CONNECTIONS AND SETTINGS 

Make  protection  zone  connections  to  the  module’s  12-position 
terminal block TB1.  Each zone that is used must have 

a 2K-ohm 

end-of-line resistor

 connected across the end of its loop, as shown 

in Figure 2.   

CE

 

 

For CE installations ADEMCO N6361 EMI 
suppression bead is required.  Refer to the 
N6361  installation  guide  for  wire  routing 
instructions.  

1. INSERT BOTTOM TABS FIRST.
2. ENGAGE TOP WITH CLIP.

4219-002-V0

 

Figure 1.  Tamper Magnet Installation 

If  a  zone  is  not  programmed,  the  resistor  need  not  be  used.    The 
method  of  programming  each  zone  for  the  type  of  alarm  and 
reporting  code  to  the  central  monitoring  station  varies  with  the 
control to which the module is connected.  Refer to the Installation 
and Setup Guide for that control unit.   

Set the DIP Switch to one of 31 addresses, as shown in Figure 3, so 
the  control  can  identify  the  module  and  communicate  with  it 
properly.    The  address  to  be  set  is  determined  by  the  particular 
control  to  be  used,  and  the  control’s  installation  instructions  must 
be  consulted.    As  shipped,  the  DIP  Switch  is  set  for  an  address  of 
“0”.   

Zone A can be set for fast response time of 10ms to an open circuit, 
if  desired,  by  setting  position  1  of  the  DIP  Switch  to  “OFF”.    As 
shipped, it is set to “ON” for a response time of 300ms, as shown in 
the table below.  All other module protection zones have a nominal 
response time of 300ms.   

Connections  to  the  control’s  keypad  wiring  points  can  be made via 
4-terminal  block  TB2  or  the  4-pin  plug  (wire  color  connections  are 
the same).   

SPECIFICATIONS 

 

Physical 

6-7/16”W x 4-1/4”H x 1-1/4” D (163mm 
x 108mm x 32mm) 

Electrical

 

 

Input Voltage: 

12VDC  (from  control’s  remote  keypad 
connection points) 

Current: 

30mA 