background image

® U.S. Registered Trademark
Copyright © 2003 Honeywell International Inc.  •  

  •  All Rights Reserved 

INSTALLATION INSTRUCTIONS

69-1372-1

32003487-001

Fan Timer

APPLICATION

The 32003487-001 Fan Timer is used to remotely control 
Honeywell heat and energy recovery ventilators. The 
timer changes the ventilator to high speed for increased 
circulation and comfort. Touching the time control pad 
selects a ventilator high-speed run time of 20 minutes.

Up to ten timers can be installed to one ventilator for 
added user convenience. Installation is quick with the 
Decora™ Switch Plate and the timer mounts in a full or 
one-half depth electrical box. The illuminated display 
shows timer status.

INSTALLATION

When Installing This Product...

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition.

2.

Check the ratings in the instructions and on the 
product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

CAUTION

Electrical Hazard.

 

Can cause personal injury or equipment dam-
age.

Disconnect power supply before installation. 
Be sure ventilator low voltage control circuit is 
disconnected from external power sources.

Wiring and Mounting

All wiring must comply with local electrical codes and 
ordinances. Refer to Fig. 1 for typical hookup.

Fig. 1. Typical hookup of fan timer to 

heat recovery ventilator.

1.

Connect the wires to the correct screw terminals as 
shown in Fig. 1.

2.

Align the timer mounting holes over the electrical 
box mounting holes.

3.

Insert and tighten the two mounting screws.

4.

Place the Decora™ Switch Plate over the timer. 
Insert and tighten the switch plate mounting 
screws. 

Setting and Display Status

1.

Press timer control pad to set the timer to 20 min-
utes. See Fig. 2. Pressing the control pad again, 
before the 20 minutes end, resets the timer to 20 
minutes.

2.

Observe that the timer indicator illuminates when 
the timer is activated and remains on for the cycle 
duration. See Fig. 2 and Table 1.

IMPORTANT

When more than one timer is installed, pressing 
the control pad on any timer resets the ventilator 
override time to 20 minutes. The indicators on 
all timers will remain illuminated for the cycle 
duration.

M14410A

1

2

DO NOT REMOVE JUMPER.

MAXIMUM WIRE LENGTH IS 100 FEET (30 METERS).
USE 20 GAUGE WIRE.

1

2

ST2

RED

BLACK

GREEN

ST3

ST1

ST4

Reviews: